background image

16

Operation and Maintenance Instructions

flow into the fan section. During extremely low ambient 
conditions, this moist air may condense and freeze on the 
cold components of the drive system. When conditions 
change and cooling is needed, any amount of ice that has 
formed on the drive system can severely damage the fans 
and fan shafts. 

Therefore, fans MUST be cycled during 

low ambient operation to avoid long periods of idle 

fan operation. Excessive cycling can damage the fan 

motors. Limit the number of cycles to a maximum of 

six per hour.

 

Two speed or pony motors offer a better method of 
control. This additional step of capacity control will reduce 
water temperature differentials and the amount of time 
that the fans are off. This method of capacity control has 
proven effective for applications where load variations are 
excessive and cold weather conditions are moderate. 

The use of a variable frequency drive provides the most 
flexible method of capacity control for forced draft units. 
The VFD control system allows the fans to run at nearly 
an infinite range of speeds to match the unit capacity to 
the system load. During periods of reduced load and low 
ambient temperatures, the fans must maintain enough 
speed to ensure positive air flow through the unit. This 
positive air flow in the unit will prevent moist air from 
migrating towards the cold fan drive components reducing 
the potential for condensation to form and freeze on 
them. The VFD control system should be implemented for 
applications that experience fluctuating loads and severe 
cold weather conditions. 

Ice Management

 

When operating an evaporative cooling unit in extreme 
ambient conditions, the formation of ice is inevitable. The key 
to successful operation is to control or manage the amount 
of ice that builds up in the unit. If extreme icing occurs, it 
can lead to severe operational difficulties as well as potential 
damage to the unit. Following these guidelines will minimize 
the amount of ice that forms in the unit leading to better 
operation during the cold weather season. 

Induced Draft Units

 

When operating an induced draft unit during the cold 
weather season, the control sequence must have a method 
to manage the formation of ice in the unit. The simplest 
method of managing the amount of ice buildup is by 
cycling the fan motors off while keeping the pump on. 
During these periods of idle fan operation, the warm water 
that is absorbing the building load flows thru the coil to 
help melt the ice that has formed in the coil, basin or louver 
areas. 

NOTE:  Using this method during periods of high winds 
can cause blow through, resulting in splash-out and ice 
formation. To help prevent blow through and splash-out, 
maintain a minimum 50% fan speed.

In more severe climates, the incorporation of a defrost 
cycle can be used to mitigate and/or eliminate any 
detrimental effects of ice in the unit. During the defrost 
cycle, the fans are reversed at half speed while the 
recirculating pump flows water through the unit’s water 
distribution system. Operating the unit in reverse will melt 

any ice or frost that may have formed in the unit or on the 
air intake louvers. The defrost cycle requires the use of 
two speed motors with reverse cycle starters or reversible 
variable frequency drives. All motors supplied by EVAPCO 
are capable of reverse operation. 

The defrost cycle should be incorporated into the normal 
control scheme of the cooler or condenser system. 
The control system should allow for either a manual or 
automatic method of controlling frequency and length of 
time required to completely defrost the ice from the unit. 
The frequency and length of the defrost cycle is dependent 
on the control methods and ambient cold weather 
conditions. Some applications will build ice quicker than 
others which may require longer and more frequent defrost 

periods. Frequent inspection of the unit will help “fine-

tune” the length and frequency of the defrost cycle. 

Forced Draft Units 

Defrost cycles are NOT recommended for forced draft 
units, since allowing the leaving water temperature set 
point to rise causes the fans to be off for very long periods 
of time. This is not recommended for forced draft coolers 
or condensers because of the potential for freezing the 
fan drive components. Therefore, the defrost cycle is 
an inappropriate method of ice management for forced 
draft units. However, low speed fan operation or variable 
frequency drives maintain a positive pressure in the 
unit which helps prevent ice formation on the fan drive 
components. 

For more information on cold weather operation, please 
download a copy of EVAPCO’s Engineering Bulletin 23 at 
evapco.com

Troubleshooting: 

see Bulletin 116-E, pages 31-33

Summary of Contents for ATC-E

Page 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Page 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Page 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Page 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Page 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Page 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Page 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Page 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Page 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Page 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Page 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Page 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Page 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Page 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Page 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Page 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Page 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Page 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Page 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Page 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Reviews:

Related manuals for ATC-E