8) Parameter group 100: Basic parameter
F140
BOOST knee-frequency (Hz)
Range: 0
– 5 Hz
Default setting: 1 Hz
F141
BOOST intensity (%)
Range: 0
– 25%
Default setting: 4 %
BOOST function allow additional voltage increase on low speed
– see graphic (for
F137=0
or
F137=1
).
F152
Maximum motor voltage (at knee frequency
–
Range: 10
– 100
%
Default setting: 100 %
modulation level)
This function is used to limit the maximum motor voltage
– the percentage value refers to the corresponding input voltage
(on 400 V power supply: 100%= 400 motor voltage)
Range:
Default setting:
0.2 - 7.5 kW:
800 Hz
– 16.000 Hz
0,2...7,5 kW:
4kHZ
F153
PWM Frequency
11
– 15 kW:
800 Hz
– 10.000 Hz
11...15 kW:
3kHz
18.5 kW
– 45 kW: 800 Hz – 6.000 Hz
18,5...45 kW:
4kHz
>55kW:
800 Hz
– 4.000 Hz
<55 kW:
2kHz
Selection: 0: deactivated
F154
Power supply voltage compensation
1: activated
Default setting: 0
2: deactivated during deceleration ramp
This function keeps the motor-voltage stable and independent from power supply voltage fluctuation. It may stretch the
deceleration phase, therefore it can be deactivated during deceleration only
(F154=2)
F155
Internal value for secondary speed reference
Range: 0…F111
Default setting: 0
F156
Polarity secondary speed ref. (direction)
Range: 0 (FWD) oder 1(REV)
Default setting: 0
F157
Secondary speed ref. readout
Read-only
F158
Secondary speed polarity readout
Read-only
Internal digital reference for secondary speed reference - analogue to F113
F159
„RANDOM“ PWM modulation
Selection: 0: constant PWM frequency
Default setting: 1
1: „RANDOM“ modulated PWM
If
F159=0:
Inverter works with constant PWM frequency (as set in
F153)
159=1:
PWM frequency is "random" over-modulated.
F160
Factory default reset
Selection: 0: Normal operation
Default setting: 0
1: Start factory default reset process
Factory default reset procedure:
Select parameter
F160
, press
SET,
original parameter F160 value is 0, press
UP
key to set F160 to
1
press
SET
again
After a few seconds all factory default parameters are restored.
The value in F160 returns to 0, after the restore process is completed.
ATTENTION:
The process will not reset to factory default the following parameters:
F400 F402 F406 F408 F412 F414 F421 F732 F742 F745 F901
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 39 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Summary of Contents for E2000-0004 S2B
Page 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Page 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...