5) Control board
– hardware and I/O channel configuration
Analogue input channels:
E1 - E6:
E2000+ inverters SIZE
E1…E6
have two independent analogue input channels
AI1
and
AI2
, both have a resolution of
12 Bit.
Signal level configuration is done by hardware setting on the control board, and corresponding parameter setting.
For software parameter setting see:
11) Parameter group 400: Configuration of analogue I/O channels
AI1
Voltage signal input:
programmable for
0….10V
or
-
10V…0…+10V
(factory-default setting 0...10V)
AI2
Voltage/Current signal input:
to configure for
0…5V, 0…10V
or
0....20 mA -
(
4...20 mA:
offset, to set via software
parameter
–
F406, F408
)
– (factory-default setting 0....20 mA)
Configuration
AI1
Factory default setting: 0...10V
Configuration
AI2
Factory default setting: 0...20mA
Input impedance for voltage control:
10 kOhm
Burden resistor for current loop:
500 Ohm
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 25 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH