11) Parameter group 400: Analog I/O configuration
Analogue output configuration
AO1, AO2
F423
Signal type configuration output
AO1
Selection: 0=0…5V
1=0…10V, 0…20mA *
Default setting: 1
current/voltage signal
2=4…20mA *
F424
Inverter output frequency assigned to
Range: 0.0…F425
Default setting: 0.05 Hz
minimum output signal on
AO1
F425
Inverter output frequency assigned to
Range: F424…F111
Default setting: 50.00 Hz
maximum output signal on
AO1
F426
Gain factor
AO1
Range: 0…120%
Default setting: 100
*) The DIP-SWITCH U/I must be set, to get current signal on AO 1 output
– see chapter
5) Control hardware and IO/
channel configuration
F427
Signal type configuration output
AO2
Selection: 0=0…20 mA
Default setting: 0
current signal only
1=4…20mA
F428
Inverter output frequency assigned to
Range: 0.0…F429
Default setting: 0.05 Hz
minimum output signal on
AO2
F429
Inverter output frequency assigned to
Range: F428…F111
Default setting: 50.00 Hz
maximum output signal on
AO2
F430
Gain factor
AO2
Range: 0…120%
Default setting: 100
F431
Assignation of operating
Selection: 0=Motor frequency
Default
parameters
1=Motor-current normalized on 2xI-n)
setting: 0
to
AO1
2=Motor-voltage (normalized on 230/400V)
3=AI1
4=AI2
5=Impulse input
F432
Assignation of
6=Torque
– normalized to m-n
7=Set via MODBUS
Default
operating parameters
8=Target frequency
setting: 1
to
AO2
9=Calculated speed
10=Torque (motoric)
Assignation motor current: The full range corresponds to 0…2x inverter rated current Assignation
motor voltage: The full range corresponds to the inverter rated voltage (230V/400V)
F433
Multiplier for motor voltage meter
Range: 0.01…5* rated value
Default setting: 2.0
F434
Multiplier for motor current meter
Default setting: 2.0
F437
Filter factor analogue output
Range: 1....100
Default setting: 10
Pulse output
DO1
:
Digital output terminal DO1 can be programmed via F303 as pulse signal output
– configuration is made in a
similar way, as for analogue outputs
F449
Max. frequency pulse output
DO1
Range: 0.00…50.00 kHz
Default: 10.00 kHz
F450
0-point offset (%)
Range: 0.
0…100.0 %
Default: 0.0%
F451
Multiplier
Range: 0.00…10.00
Default: 1.00
Selection:0=Motor frequency
1=Motor-current normalized on 2xI-n)
2=Motor-voltage (normalized 230/400V)
F453
Assignation of
3=AI1
4=AI2
operating parameters
5=Impulse input
Default setting: 0
to
DO1
6=Torque
– normalized to m-n
7=Set via MODBUS
8=Target frequency
9=Calculated speed
10=Torque (motoric)
E2000+_Rev.02 -E- SOFT Rev. 5.09
- 52 -
© 2016-06-KPP-EURADRIVES EUROPE GmbH
Summary of Contents for E2000-0004 S2B
Page 24: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 27: ...E2000 _Rev 02 D SOFT Rev 5 09 22 2016 06 KPP EURADRIVES EUROPE GmbH...
Page 47: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 49: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 55: ...2016 06 KPP EURADRIVES EUROPE GmbH...
Page 63: ...2016 06 KPP EURADRIVES EUROPE GmbH...