Images are for illustrative purposes.
We reserve the right to make changes.
RDT-59-0322
13
®
NORD
canopy
|
EOZ installation guide
5. Electrical Installation
The EOZ 3.1 External Ozone Cleaning System must be interlocked with the exhaust system, so that when the
exhaust ventilation is not running, no electrical power is supplied to the ozone system. See the sample diagram
below as one possible option to accomplish this function.
A maximum of 4 Ozone Modules and one alarm panel may be connected a single 10A C-type (slow) circuit
breaker. Remember to label the circuit breakers used in the distribution board.
NOTE
! Electrical installation must be performed by an authorized electrician and follow local, regional
and national standards and regulations.
F1
F2
K1
KL1
<I
L1
N
L1
DISTRIBUTION BOARD NO. 1
DISTRIBUTION BOARD NO. 2
VENTILATION UNIT
F1 - Circuit breaker
F2 - EOZ Control Panel
Current relay
(0...100%)
AC relay
Motor, exhaust ventilation fan s
motor drive
EOZ
<I
K
Junction box
<I
I/O
Building automation
PLC
Modbus
BACnet (TCP/IP)
ModBus (TCP/IP)
Ethernet (TCP/IP)
Control Panel