Connector J10
contains 120V AC connections
Pin 1
- 120VAC Input from Evap Cooler Pressure
Switch
Pin 2
- 120VAC Input from Evap Cooler Float
Switch
Pin 3
- 120VAC Output to Evap Cooler Water
Solenoid
Pin 4
- 120VAC Output to Evap Cooler 3-way Drain
Valve
Pin 5
- 120VAC Input from Supply Overload
Pin 6
- 120VAC Output to Supply Starter Coil
Pin 7
- 120VAC Output to Exhaust Starter Coil
Pin 8
- 120VAC Input from Exhaust Overload
Connector J11
contains low voltage screw terminal
connections
Pin 1
- 24VAC Auxiliary Input
Pin 2
- 24VAC Auxiliary Input
Pin 3
- 24VAC Auxiliary Input
Pin 4
- 24VAC Call for Heat Input
Pin 5
- 24VAC Call for Cooling Input
Pin 6
- 24VAC Call for Blower Input
Pin 7
- 24VAC Occupied Override Input
Pin 8
- 24VAC Isolated Common
Connector J12
contains low voltage screw terminal
connections
Pin 1
- 24VAC Output to Smoke Detector
Pin 2
- 24VAC Output to Smoke Detector
Pin 3
- 24VAC Digital Input from Smoke Detector
Pin 4
- 24VAC Common to Smoke Detector
Pin 5
- 24VAC Output to Air Quality Sensor
Pin 6
- 0-10V Analog Input from Air Quality Sensor
Pin 7
- 24VAC Common to Air Quality Sensor
Pin 8
- 24VAC Common to Air Quality Sensor
1
8
AUX
IN1
AUX
IN2
AUX
IN3
HEAT
COOL
FAN
OCC
OVR
ISO
COM
W Y G
1
8
BAS/STAT
24V AC
COM
24V AC
IN
DI-1
COM
24V AC
VIN
AI-1
0-10
COM