41
Menu Tree
User Settings
NOTE: If scheduling is On, occupied and unoccupied settings will be available for some
parameters.
HEAT (OCC/UNOCC)
HEAT (OCC/UNOCC)
MIN (OCC/UNOCC)
MAX (OCC/UNOCC)
ROOM OVERRIDE
FIRESTAT SET POINTS
FREEZESTAT SET POINTS
CAB HEAT SET POINT
WARM LIQ SET POINTS
INTAKE (OCC/UNOCC)
SPACE (OCC/UNOCC)
COOL (OCC/UNOCC)
EVAP (OCC/UNOCC)
COOL (OCC/UNOCC)
EVAP DRAIN SET POINT
OA RESET HIGH
OA RESET LOW
RESET HEAT DISCHARGE
RANGE: 100-300°F/38-149°C
DEFAULT: 135°F/57°C
RANGE: 100-300°F/38-149°C
DEFAULT: 240°F/101°C
RANGE: (-40)-75°F/(-40)-24°C
DEFAULT: 35°F/2°C
RANGE: 0-40°F/(-18)-4°C
DEFAULT: 0°F/-18°C
RANGE: 0-50°F/(-18)-10°C
DEFAULT: 35°F/2°C
RANGE: 35-50°F/2-10°C
DEFAULT: 40°F/4°C
RANGE: 0-50°F/(-18)-10°C
DEFAULT: 35°F/2°C
RANGE: 35-110°F/2-43°C
DEFAULT: 45°F/7°C
RANGE: 35-110°F/2-43°C
DEFAULT: 70°F/21°C
RANGE: 40-160°F/4-71°C
DEFAULT: 50°F/4°C
RANGE: 40-160°F/4-66°C
DEFAULT: 150°F/65°C
RANGE: 40-150°F/4-66°C
DEFAULT: 90°F/31°C
RANGE: 0-20°F/0-13°C
DEFAULT: 10°F/6°C
RANGE: 0-20°F/0-13°C
DEFAULT: 2°F/2°C
INTAKE
DISCHARGE
FREEZESTAT
CAB HEAT
STAGE 1
RANGE: 55-120°F/13-50°C
DEFAULT: 85°F/29°C
RANGE: 55-100°F/13-38 °C
DEFAULT: 85°F/29°C
RANGE: 55-120°F/10-32°C
DEFAULT: 74°F/23°C
EVAP DRAIN
STAGE 2
USER SETTINGS
TEMP SET POINTS
INTAKE SET POINTS
SPACE SET POINTS
DISCHARGE LIMITS
DISCHARGE SET POINTS
DIFFERENTIALS
OPTION SET POINTS
HEAT
RANGE: 40-150°F/4-66°C
DEFAULT: 55°F/13°C
RANGE: 35-110°F/7-43°C
DEFAULT: 45°F/7°C
RANGE: 40-150°F/4-65°C
DEFAULT: 90°F/32°C
RANGE: 35-110°F/7-43°C
DEFAULT: 75°F/24°C
RESET COOL SPACE
RESET HEAT SPACE
RANGE: (-10)-10°F/(-6)-6°C
DEFAULT: 2°F/1°C
RANGE: (-10)-10°F/(-6)-6°C
DEFAULT: 2°F/1°C