45
Factory Settings - Password 1111
NOTE: If scheduling is On, occupied and unoccupied settings will be available for some
parameters.
FACTORY SETTINGS
BLOWER CONTROL
120V CONTACTOR (DEFAULT), VFD MANUAL,
VFD PRESET, VFD JOG, VFD 0-10V, VFD PRESSURE,
ECM, ECM 0-10V, ECM PRESET, ECM PRESSURE, ECP
BLOWER MODE
OCC/UNOCC
AUTO, OFF, ON
DEFAULT: AUTO
POST PURGE CONFIG
ON/OFF
DEFAULT: ON
ENABLE
PURGE TIME
RANGE: 0-600 S
DEFAULT: 30 S
VFD DIRECTION
FORWARD/REVERSE
DEFAULT: FORWARD
DIRECTION
VFD FREQ LIMITS
OCC/UNOCC MIN
OCC/UNOCC MAX
RANGE: 0-MAX FREQ
DEFAULT: 0.0 HZ
RANGE: MIN FREQ- 80
DEFAULT: 80 HZ
PWM RATE LIMITS
OCC/UNOCC MIN
OCC/UNOCC MAX
RANGE: 0-100%
DEFAULT: 0%
RANGE: 0-100%
DEFAULT: 100%
BLOWER CONFIG
UNIT OPTIONS
PRESSURE CONFIG
BLOWER PRESETS
ON/OFF
DEFAULT: OFF
DOOR INTERLOCK
ON/OFF
DEFAULT: OFF
SENSOR RANGE
STATIC PS KP
RANGE: 0.10 V/S - 0.50 V/S
DEFAULT: 0.15 V/S
OCC FAN PRESETS
RANGE: 0-80 HZ
DEFAULT: VARIES
PRESET (0-7)
PRESET 0 = 0 Hz
PRESET 1 = 40 Hz
PRESET 2 = 50 Hz
PRESET 3 = 60 Hz
PRESET 4 = 0 Hz
PRESET 5 = 0 Hz
PRESET 6 = 0 Hz
PRESET 7 = 0 Hz
UNOCC FAN PRESETS
RANGE: 0-80 HZ
DEFAULT: VARIES
PRESET (0-7)
FAN PRESETS DEFAULT
OCC PWM PRESETS
RANGE: 0-100%
DEFAULT: VARIES
PRESET (0-7)
PRESET 0 = 0%
PRESET 1 = 80%
PRESET 2 = 90%
PRESET 3 = 100%
PRESET 4 = 0%
PRESET 5 = 0%
PRESET 6 = 0%
PRESET 7 = 0%
UNOCC PWM PRESETS
RANGE: 0-100%
DEFAULT: VARIES
PRESET (0-7)
VFD VOLT LIMITS
OCC/UNOCC MIN
RANGE: 0-10 V
DEFAULT: 0 V
VFD BY OTHERS
ENABLE
ON/OFF
DEFAULT: OFF
ENABLE
OCC/UNOCC MAX
RANGE: 0-10 V
DEFAULT: 10 V
ENABLE
RANGE: +/- .25" W.C. or +/- 5" WC
DEFAULT: +/- .25" W.C.
PWM PRESETS DEFAULT
CYCLE TIME
PS HYSTERESIS
RANGE: 5-60 S
DEFAULT: 5 S
RANGE: (-5.00)-5.00”
DEFAULT: 0.25”
FAN PROVING CONFIG
OFF/PROVING
DEFAULT: OFF
ENABLE
1/2
DEFAULT: 1
# OF CONTACTORS