Factory Settings - Password 1111
NOTE: If scheduling is On, occupied and unoccupied settings will be available for some
parameters.
NOTE: When Average HMI is set to more than 1, each HMI will have an averaging On/Off setting.
COOLING CONFIG
COOLING TYPE
NONE/DX/EVAP/BOTH
MIN COOL OA TEMP
RANGE: 40-90°F/4-32°C
DEFAULT: 55°F/13°C
COOL HYST
SPACE
INTAKE
RANGE: 0-2°F/0-1°C
DEFAULT: 1°F/1°C
RANGE: 0-10°F/0-6°C
DEFAULT: 3°F/2°C
EVAP CONFIG
SPRAYER TIMES
EVAP DRAIN
EVAP HYST
TIME OFF
TIME ON
RANGE: 0-60 S
DEFAULT: 15 S
RANGE: 0-500 S
DEFAULT: 60 S
ENABLE
ON/OFF
DEFAULT: OFF
HYST
RANGE: 0-10°F/0-6°C
DEFAULT: 1°F/1°C
DRAIN HYST
RANGE: 1-5°F/1-3°C
DEFAULT: 2°F/1°C
FACTORY SETTINGS
CONDENSER STAGING
NONE (DEFAULT), 1 COND 1 STAGES, 2 COND 2 STAGES,
2 COND 3 STAGES, 3 COND 2 STAGES, 3 COND 3 STAGES
CONDENSER MIN TIMES
MIN ON
MIN OFF
RANGE: 1-15 M
DEFAULT: 2 M
RANGE: 1-15 M
DEFAULT: 1 M
UNIT OPTIONS
BOARD CONFIG
UNIT ADDRESS
RANGE: 75-89
DEFAULT: 85
STARTUP TIMER
RANGE: 5-240 S
DEFAULT: 5 S
TIME
TEMP READINGS
MODE
FAHRENHEIT/CELSIUS
DEFAULT: FAHRENHEIT
HMI CONFIG
NUMBER
SCREENSAVER
RANGE: 1-5
DEFAULT: 1
ON/OFF
DEFAULT: ON
OCCUPANCY CONFIG
SCHEDULING
ON/OFF
DEFAULT: OFF
OVERRIDE
ON/OFF
DEFAULT: ON
AVERAGE HMI
LOCK SCREEN
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
SCNSVR DISP MODE
DATE/TIME
TEMP/DATE/TIME
TEMP