Figure 10 - Gas Connection Diagram
Table 5 - Gas Pressure
Gas Pressure Type
Gas Pressure
Size 1-3 Inlet
7 -14 Inches WC
Size 4-5 Inlet
7 Inches WC - 5 psi
Maximum Manifold Pressure - Natural Gas
5 Inches WC Maximum
Maximum Manifold Pressure - Propane
2.5 Inches WC Maximum
NOTICE
Refer to the heater’s rating plate for determining gas supply pressures and requirements.
1
1
2
3
4
5
A
1. Gas Supply Line Connection
2. Manual Gas Shut-off Valve
3. Ground Joint Union with Brass Seat
4. Plugged 1/8” NPT Test Gauge Connection
5. Sediment Trap
A. Minimum Depth = 3”