18
Note: Some connections may not be used dependent on system configurations
RJ45 connectors.
Connector J1
and
J2
are associated with BMS.
Connector J3
through
J6
are interchangeable and
may be used to connect to an HMI or VFD.
J1
- CASLink/Slave
J2
- CASLink/Slave
J3
- HMI/VFD/Master
J4
- HMI/VFD/Master
J5
- HMI/VFD/Master
J6
- HMI/VFD/Master
Connector J7
contains inputs and outputs for the
Flame Safety Controller (FSC)
Pin 1
- N/A
Pin 2
- 24VAC Pilot Valve
Pin 3
through
Pin 8
- N/A
Pin 9
- 24VAC Common to Main/Pilot Gas Valve
Pin 10
through
Pin 18
- N/A
Connector J8
contains inputs and outputs for the
Flame Safety Controller (FSC)
NOTE: Connector J8 only for Compact Models
Pin 1
- N/A
Pin 2
- 24VAC Pilot Valve
Pin 3
through
Pin 8
- N/A
Pin 9
- 24VAC Common to Main/Pilot Gas Valve
Pin 10
through
Pin 18
- N/A
Connector J9
contains 120V AC connections
Pin 1
- 120VAC Main Input
Pin 2
- 120VAC Input from Discharge Damper End
Switch
Pin 3
- 120VAC Input from Fire Micro-Switch
Pin 4
- 120VAC Output to Intake/Discharge Damper
Actuator
Pin 5
- 120VAC Input from Intake Damper End
Switch
Pin 6
- N/A
Pin 7
- 120VAC Output to Cabinet Heater
Pin 8
- 120VAC Neutral
J2
J1
J3
J4
J5
J6
1
9
10
18
1
9
10
18
1
8