www.esylux.com
5 13
/
PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)
GB
DESCRIPTION OF APPLICATIONS
1 • MASTER/SLAVE SELECTION
The Master detects presence and evaluates it according to set parameters.
Lighting ON/OFF or lighting light value higher/lower.
The Slave is used exclusively for extending the field of detection.
A presence is transferred to the Master (Object 14) for evaluation
according to the set parameters.
•
Master/Master selection
To extend the field of detection, two Masters can work in parallel.
Each Master evaluates the presence (Object 13 and 14) according to
its parameters set via the ETS (Engineering Tool Software) and controls
the lighting appropriately.
Default setting: Master
2 • TEST MODE OFF/ON
(Only for Master device configuration)
When test mode ON
➞
light measurement deactivated.
When test mode is enabled, the connection with the lighting
system is checked.
In the event of detection, the lighting will be ON for 5 sec.,
followed by a dead time of 5 sec. OFF.
The LED display is enabled.
Test ON changes to test OFF automatically after 10 min. or when
parameters are stored.
NOTE: During test
➞
Slave input enabled.
Default setting: Test OFF