background image

www.esylux.com

1 13

/

PRESENCE DETECTOR      PD-C360i/24 KNX ECO      (EP10425844)

GB

PRäSENzmElDER

D

Congratulations on your purchase of this high-quality ESYLUX product. To ensure proper operation, 

please read these user instructions carefully and keep them for future reference

1 • SAFETY INSTRUCTIONS

 

CAUTION: Work on the 230 V power system must be carried out by authorised personnel only

   

with due regard to the applicable installation regulations. Switch off the power supply before 

   

installing the system.

Use this product only as intended (as described in the user instructions). Changes or 

modifications to the product or painting it will result in loss of warranty. 

You should check the device for damage immediately after unpacking it. 

If there is any damage, you should not install the device under any circumstances.

If you suspect that safe operation of the device cannot be guaranteed, you should turn 

the device off immediately and make sure that it cannot be operated unintentionally.

2 • DESCRIPTION

The ESYLUX PD-C360i/24 KNX ECO is a presence detector with a 360° field of detection 

and integrated bus coupler for ceiling mounting. The detector is able to control lighting 

(switching or constant light control features).

For further features, please refer to the operating instructions 

“Description of applications”

.

With a range of up to 24 m in diameter, the presence detector is suitable for use in 

offices, classrooms, conference facilities and halls with natural lighting.

The PD-C360i/24 KNX ECO is intended to be used in a KNX (EIB), TP bus system in con-

junction with other KNX components.

If the ESYLUX PD-C360i/24 KNX ECO detects that persons are present in its field of 

detection, it transmits controlling telegrams for light outputs, depending on ambient 

brightness, and for HVAC (heating, ventilation and air conditioning) objects.

• Blended light measurement is suitable for FL, PL, halogen and incandescent lamps.

Certified KNX/EIB training centres provide specialist training on how to plan, install, 

activate, document and apply the ETS (Engineering Tool Software) that is required for 

parameter setting.

3 • INSTALLATION / ASSEMBLY / CONNECTION

  See separate assembly instructions.

4 • START-UP

All parameter setting is carried via the ETS (Engineering Tool Software).

The product database and application description are available to download 

at www.esylux.com.

5 • SWITCH-ON CHARACTERISTIC / LED INDICATIONS

• 

Connect the bus supply

  A warm-up phase of approx. 25 sec. is initiated. 

  The 

red LED

 and 

green LED

 flash slowly (f = 1 Hz).

•  LED display after warm-up

  Each time motion is detected, this is indicated by 2 x flashes of the 

green LED

.

•  In the Master function, the remote control entries will be acknowledged as follows:

  acknowledged 3 x with the 

red LED

•  In the Slave function

, each detection is acknowledged 2 x with the 

green LED

.

  NOTE: The green LED will only light up when motion is detected if it has been

   

enabled by the ETS (Engineering Tool Software).

6 • TEST MODE

Parameters can be set via the ETS (Engineering Tool Software).

Test mode changes to RUN state after “storing” or 10 min. after activating the test mode.

7 • REMOTE CONTROL

The optional user remote control Mobil-PDi/User (EM10425547) can be used to 

control lighting.

The Mobil-PDi/User adjusts the value for the period that persons are present plus 

switch-off delay time. Thereafter the values set via the ETS (Engineering Tool Software) 

will apply.

  NOTE: In the Slave function the detector does not respond to the remote control.

The lighting can be controlled as follows via the Mobil-PDi/User:

• Switching on or off

• Dimming (only with “Controlling” feature)

• Storing and calling up of 2 scenes

• Pressing the Reset button resets the KNX presence detector to the values set 

  via ETS (Engineering Tool Software).

  The stored light scenes 1 + 2 are kept.

For further information, please refer to the operating 

instructions for the remote control Mobil-PDi/User.

8 • ESYLUX MANUFACTURER’S GUARANTEE

ESYLUX products are tested in accordance with applicable regulations and manufactured 

with the utmost care. The guarantor, Elektro-Technische-Systeme GmbH, Postfach 1840, 

D-22908 Ahrensburg, Germany (for Germany and Austria) or the relevant ESYLUX 

distributor in your country (visit www.esylux.com for a complete overview) provides a gua-

rantee against manufacturing/material defects in ESYLUX devices for a period of 

three years from the date of manufacture.

This guarantee is independent of your legal rights with respect to the seller of the device.

The guarantee does not apply to natural wear and tear, changes/interference caused by 

environmental factors or damage in transit, nor to damage caused as a result of failure to 

follow the user or maintenance instructions and/or as a result of improper installation.

Any illuminants or batteries supplied with the device are not covered by the guarantee.

The guarantee can only be honoured if the device is sent back with the invoice/receipt, 

unchanged, packed and with sufficient postage to the guarantor, along with a brief 

description of the fault, as soon as a defect has been identified.

If the guarantee claim proves justified, the guarantor will, within a reasonable period, 

either repair the device or replace it. The guarantee does not cover further claims; in 

particular, the guarantor will not be liable for damages resulting from the device’s 

defectiveness. If the claim is unfounded (e.g. because the guarantee has expired or the 

fault is not covered by the guarantee), then the guarantor may attempt to repair the 

device for you for a fee, keeping costs to a minimum.

 Mobil-PDi/User

PRESENCE DETECTOR

GB

www.esylux.com

• 

•  PD-C360i/24 KNX ECO

Summary of Contents for PD-C360i/24 KNX ECO

Page 1: ...owledged 3 x with the red LED In the Slave function each detection is acknowledged 2 x with the green LED NOTE The green LED will only light up when motion is detected if it has been enabled by the ET...

Page 2: ...ck No change Switch off Switch on Object 1 Input light Switches between the orientation light values with constant light control feature An ON telegram changes the setting from orientation light value...

Page 3: ...PUTS Object 5 Output light on off Feature Switching Constant light control If persons are present and artificial lighting is required the output sends an ON telegram If natural light is sufficient and...

Page 4: ...are present an OFF telegram is sent once the switch off delay time has elapsed Optional offset dim value 2 to dim value 1 50 to 50 Object 9 Output light value The output light value transmits every 1...

Page 5: ...two Masters can work in parallel Each Master evaluates the presence Object 13 and 14 according to its parameters set via the ETS Engineering Tool Software and controls the lighting appropriately Defa...

Page 6: ...lt setting ON 4 SWITCH OFF TIME PRESENCE OUTPUT HVAC Option of selecting a switch off time delay of 0 sec 10 sec or 1 min 60 min NOTE The presence output is independent of the set light values Default...

Page 7: ...be smaller than the light value on the work surface below The difference varies greatly and is dependent on local conditions Dark surfaces cause a low level of reflection Light matte surfaces cause a...

Page 8: ...an be switched on or off manually at any time using infrared remote control Mobil PDi User please also refer to separate Mobil PDi User instructions or by telegrams e g by pressing external KNX EIB bu...

Page 9: ...switch off delay time has elapsed The lighting can subsequently be switched back on manually at any time If the artificial light has been switched on manually due to low ambient brightness conditions...

Page 10: ...ght control Default setting Switching 12 THRESHOLD SWITCHING Options 0 disabled Options 1 lux 2000 lux up down menu or direct entry 0 lux 2000 lux Default setting 500 lux There is an option of determi...

Page 11: ...n Default setting 5 min 15 CONSTANT LIGHT CONTROL Control timing Options 0 5 sec 10 sec up down menu NOTE If the control loop exhibits a hunting tendency the sensor can be adjusted to various illumina...

Page 12: ...rol NOTE The orientation light value 1 is active as standard Via Object 1 an ON telegram changes the setting to orientation light value 2 and an OFF telegram changes the setting to orientation light v...

Page 13: ...ways on if the light falls below the set value 1 min 250 min up down menu or as direct entry 0 min 250 min applies to both orientation light values NOTE Only active for constant light control NOTE Onl...