PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)
GB
Object 7
Output light, dim value 1
*Feature: Constant light control
If persons are present and artificial lighting is required, the output sends an ON/value telegram (1 byte).
If natural light is sufficient (controller to minimum) and/or no persons are present, an OFF telegram is sent
once the switch-off delay time has elapsed.
Object 8
Output light, dim value 2
*Feature: Constant light control
If persons are present and artificial lighting is required, the output sends an ON/value telegram (1 byte).
If natural light is sufficient (controller to minimum) and/or no persons are present, an OFF telegram is sent
once the switch-off delay time has elapsed.
*Optional offset dim value 2 to dim value 1: -50% to +50%
Object 9
Output light value
The output light value transmits, every 1 min. - 30 min. (depending on the telegram interval selected),
the current lux value (2 byte) measured at the presence detector.
Object 10
Output state
The output state transmits the current status as a telegram every 1 min. - 30 min.,
depending on the telegram interval selected.
No interference = OFF telegram
Interference
= ON telegram
Object 12
Output presence (HVAC) on/off
If persons are detected, depending on the turn-on delay, an ON telegram is sent.
If no persons are detected, depending on the switch-off delay time, an OFF telegram is sent.
Object 14
Output own presence
Trigger output for parallel connection of Master/Master or output of Slave.