PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)
GB
Object 4
Input light, dim value manually
*Feature: Constant light control
Input for presetting dim values (1 byte)
Object 11
Input presence lock
The output presence (Object 12) is locked by an ON telegram.
This is unlocked with an OFF telegram.
Options for change in state after presence lock:
- No change
- Switch off
- Switch on
Object 13
Input presence
Trigger input for parallel connection of Master/Master or input of Slave.
Object 15
Input reset
Resets the presence detector (see page 8 for behaviour at reset)
OUTPUTS
Object 5
Output light, on/off
*Feature: Switching/Constant light control
If persons are present and artificial lighting is required, the output sends an ON telegram.
If natural light is sufficient and/or no persons are present, an OFF telegram is sent once the
switch-off delay time has elapsed.
Object 6 (switching)
Output light, on/off
*Feature: Switching
If persons are present and artificial lighting is required, the output sends an ON telegram.
If natural light is sufficient and/or no persons are present, an OFF telegram is sent once the
switch-off delay time has elapsed.
Object 6 (optional dimming)
Output light, dim
*Feature: Constant light control
If the touch sensor (Object 3) is manually pressed and held, the dim values of the presence detector
are overwritten via this output.