background image

www.esylux.com

13 13

/

PRESENCE DETECTOR      PD-C360i/24 KNX ECO      (EP10425844)

GB

ESYLUX GmbH

Postfach 1834, 22908 Ahrensburg/Germany

Internet: www.esylux.com, e-mail: [email protected]

SAM 

11/2009

18 • ORIENTATION LIGHT DURATION

0 = always on (if the light falls below the set value) 

1 min. - 250 min. (up/down menu) or 

as direct entry 0 min. - 250 min. (applies to both orientation light values)

 

NOTE: Only active for constant light control.

 NOTE: Only active if orientation light has been set to ON.

[0,1...250 min.]

Default setting: 5 min.

19 • OFFSET DIMM VALUE 1/2

There is an option of determining an offset between:

Dimm value 1 and 
dimm value 2

-50% to +50%

Default setting: ±0%

Summary of Contents for PD-C360i/24 KNX ECO

Page 1: ...owledged 3 x with the red LED In the Slave function each detection is acknowledged 2 x with the green LED NOTE The green LED will only light up when motion is detected if it has been enabled by the ET...

Page 2: ...ck No change Switch off Switch on Object 1 Input light Switches between the orientation light values with constant light control feature An ON telegram changes the setting from orientation light value...

Page 3: ...PUTS Object 5 Output light on off Feature Switching Constant light control If persons are present and artificial lighting is required the output sends an ON telegram If natural light is sufficient and...

Page 4: ...are present an OFF telegram is sent once the switch off delay time has elapsed Optional offset dim value 2 to dim value 1 50 to 50 Object 9 Output light value The output light value transmits every 1...

Page 5: ...two Masters can work in parallel Each Master evaluates the presence Object 13 and 14 according to its parameters set via the ETS Engineering Tool Software and controls the lighting appropriately Defa...

Page 6: ...lt setting ON 4 SWITCH OFF TIME PRESENCE OUTPUT HVAC Option of selecting a switch off time delay of 0 sec 10 sec or 1 min 60 min NOTE The presence output is independent of the set light values Default...

Page 7: ...be smaller than the light value on the work surface below The difference varies greatly and is dependent on local conditions Dark surfaces cause a low level of reflection Light matte surfaces cause a...

Page 8: ...an be switched on or off manually at any time using infrared remote control Mobil PDi User please also refer to separate Mobil PDi User instructions or by telegrams e g by pressing external KNX EIB bu...

Page 9: ...switch off delay time has elapsed The lighting can subsequently be switched back on manually at any time If the artificial light has been switched on manually due to low ambient brightness conditions...

Page 10: ...ght control Default setting Switching 12 THRESHOLD SWITCHING Options 0 disabled Options 1 lux 2000 lux up down menu or direct entry 0 lux 2000 lux Default setting 500 lux There is an option of determi...

Page 11: ...n Default setting 5 min 15 CONSTANT LIGHT CONTROL Control timing Options 0 5 sec 10 sec up down menu NOTE If the control loop exhibits a hunting tendency the sensor can be adjusted to various illumina...

Page 12: ...rol NOTE The orientation light value 1 is active as standard Via Object 1 an ON telegram changes the setting to orientation light value 2 and an OFF telegram changes the setting to orientation light v...

Page 13: ...ways on if the light falls below the set value 1 min 250 min up down menu or as direct entry 0 min 250 min applies to both orientation light values NOTE Only active for constant light control NOTE Onl...

Reviews: