Installation and connection
Doc. no. BA012497_02
29 / 107
GB
If you connect several Light Control Boxes to connected DALI
detectors in parallel, you can choose which detector is responsible
for measuring the room lighting. See section “8.13 Light value
67 for more information about this
setting.
If you subsequently connect a Light Control Box in parallel to a
preset Light Control Box, the devices save different settings. If
this is the case, reset the preset Box to factory settings and re-en-
ter the settings for the connected Light Control Boxes.
The Box can be restored to factory settings using the universal re-
mote control (see Chapter 8.9 on page 65) and using the app (see
Chapter 13.1.8 on page 90).
4.4 Warm-up phase
The Light Control Box starts the warm-up phase each time the power is
switched on.
Configuring the Light Control Box during the warm-up phase:
• Connected lights are on.
•
The red and green LEDs in the presence detector flash alternately five
times.
• After approx. 15 seconds, the Light Control Box is ready for opera-
tion and functions in line with the factory settings or the user-defined
program.
Once the warm-up phase is complete, the LED signals on the
presence detector mean the following: Red LED = remote control
command is being received; green LED = presence detected; blue
LED = Light Control Box is in programming mode.
4.5 Factory settings
The Light Control Boxes are configured with factory settings. These defaults
can be changed according to preference. ESYLUX recommends noting down
the changed settings in the right-hand column of the table.
Settings
Default
Individual setting
Operating mode
fully automatic
Brightness target value
500 lux
Off delay time
5 minutes
Orientation light
Brightness 10%
Duration of orientation light
0 minutes
Switch-off warning channel 1–4 60 seconds
Choose
detector
Parallel con-
nection after
installation