E-S 500 / 502 Classic Series Instruction Manual
5.7
Control Board Overview
Light:
Sends pulses of 24VDC only while gate is running, and whether it is open
or closed.
Motor 1:
L1-1, L1-2 = 24VDC power to single motor or master motor
Motor 2:
L2-1, L2-2 = 24VDC power to slave motor
Limit 1:
OL1 = Open limit for single motor or master (normally closed)
V+ = Common for limits, +12VDC
CL1 = Closed limit for single motor (normally closed)
Limit 2:
OL2 = Open limit for slave motor (normally closed)
V+ = Common for limits, +12VDC
CL2 = Closed limit for slave motor (normally closed)
Photocell:
Photo = Input for safety eye photo beam connection (normally closed)
GND = Ground for photocell power/ground for photo connection
V+ = +12VDC, Max 100 milliamps for photocell power
+24V = +24VDC, Max 200 milliamps for accessory power
Button:
PUSH 1 = Ground for Push 1 Accessory
*
PUSH 1 / V+ is for push buttons, keypads, receivers, or any other dry
and momentary contact.
COM = Positive v12VDC for Push 1 or Push 2 accessory (relay
only, not main power)
PUSH 2 = Ground for Push 2 accessory
*
PUSH 2 / V+ is for exit wand, exit loops or other open only dry contact
and momentary contact
E_Lock:
Solenoid lock output - 12VDC (4 Amp max)
A = Positive B = Negative
Fuses:
F1 = 8A 250V, protects motor 1
F2 = 8A 250V, protects motor 2
F3 = 2A 250V, protects accessory 24V
Summary of Contents for E-S 500
Page 5: ......
Page 10: ...E S 500 502 Classic Series Instruction Manual SECTION 2 Installation of Mounting Brackets ...
Page 11: ......
Page 26: ......
Page 36: ...E S 500 502 Classic Series Instruction Manual SECTION 4 Start Up and Operation ...
Page 37: ......
Page 45: ......