26
SAN Annunciator Manual
Application
The SIN-16 provides input circuits for normally open dry relay contacts
or open collector transistor inputs. The high circuit density makes the
SIN-16 module ideal for inputting multiple switching functions from
graphic annunciators or interfacing to outside systems. Active SIN-16
inputs generate a supervisory open condition.
Specifications
Specifications
Power
From SAN-CPU
Standby Current
1 mA
Input Current
7 mA/Ckt.
Input Voltage
24 VDC Max.
Weight (oz)
4.3
Address Requirements:
Inputs
Outputs
16 (2 groups of eight)
None
Installation
The SIN-16 may be installed in the SAN-4, SAN-8, or RSAN-6
enclosures. For integral mounting within a custom annunciator
enclosure, the board only version (without mounting plate) may be
ordered.
The SIN-16 module requires two groups of 8 input addresses of the
SAN-CPU to which it is connected.
Jumper Setup
JP1
Install JP1 if the SIN-16 is the last module installed on the data
line.
Field Wiring
Plug the ribbon cable assembly (P/N 250080) form the previous SAN
series module into P2 and plug the ribbon cable into P1 on the next
SAN series module.
TB2-1 (+) common for SIN-16 inputs 1 to 4 (TB1-1 to TB1-4)
TB2-2 (+) common for SIN-16 inputs 5 to 8 (TB1-5 to TB1-8)
TB2-3 (+) common for SIN-16 inputs 9 to 12 (TB1-9 to TB1-12)
TB2-4 (+) common for SIN-16 inputs 13 to 16 (TB1-13 to TB1-16)