SAN Annunciator Manual
29
Application
The SRU-8 provides normally open/normally closed dry relay contacts.
Specifications
Specifications
Power
From SAN-CPU
Standby Current
1 mA
Relay Current
20 mA/Relay
Contacts
24 VDC, 4A Max.
Address Requirements:
Inputs
Outputs
None
8 (1 group of eight)
Installation
The SRU-8 may be installed in the SAN-4, SAN-8, or RSAN-6
enclosures.
The SRU-8 module requires one group of 8 output addresses of the
SAN-CPU to which it is connected.
Jumper Setup
JP1
Install JP1 if the SRU-8 is the last module installed on the data
line.
Field Wiring
Plug the ribbon cable assemble (P/N 250080) from the previous SAN
series module into P2 and plug the ribbon cable into P1 on the next
SAN series module.
TB1-1: K1 NC
TB1-2: K1 COM
TB1-3: K1 NO
TB1-4: K2 NC
TB1-5: K2 COM
TB1-6: K2 NO
TB1-7: K3 NC
TB1-8: K3 COM
TB1-9: K3 NO
TB1-10: K4 NC
TB1-11: K4 COM
TB1-12: K4 NO
TB2-1: K1 NC
TB2-2: K1 COM
TB2-3: K1 NO
TB2-4: K2 NC
TB2-5: K2 COM
TB2-6: K2 NO
TB2-7: K3 NC
TB2-8: K3 COM
TB2-9: K3 NO
TB2-10: K4 NC
TB2-11: K4 COM
TB2-12: K4 NO