SAN Annunciator Manual
Application
The SWU-8 provides point status indication and switching functions at
a location remote from the main control panel. Typical applications
include audio or fire fighters telephone zone select, audio zone silence,
and manual control/override of automatic systems.
Specifications
Specifications
Power
From SAN-CPU
Standby Current
1 mA
Alarm Current
6 mA / LED
Weight (oz)
3.3
Address Requirements:
SWU-8
Inputs
Outputs
SWU-8/3
Inputs
Outputs
8 (1 group of eight)
16 (2 groups of eight)
16 (2 groups of eight)
16 (2 groups of eight)
Installation
The SWU-8 and SWU-8/3 may be installed in the SAN-4, SAN-8, or
RSAN-6 enclosures. Enter the appropriate switch and LED
identification information on the label strip before installing it in the
SWU-8 or SWU-8/3.
The SWU-8 module requires one group of 8 input addresses and two
groups of 8 output addresses of the SAN-CPU to which it is connected.
The SWU-8/3 module requires two groups of 8 input addresses and two
groups of 8 output addresses of the SAN-CPU.
Field Wiring
The only wiring required is to plug the ribbon cable assembly (P/N
250080) from the previous SAN series module into P2 and plug the
ribbon cable assembly into P1 of the next SAN series module.
Jumper Setup
JP1
Install JP1 if the SWU-8/3 Module is the last module on the
ribbon cable chain.
Indicators and Controls
Eight switches and 16 LEDs are individually programmed and
controlled by the system software.