IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 23 of 29
Revised 10/21/2013
13.0
Certifications
The
IPES–IR/UV
meets
the
following
certifications:
FM
(U.S.
&
Canada)
Hazardous
Locations
Zone
Locations
Class
I,
Zone
1,
AEx
d
IIC,
T5,
Gb
1.
ISO
Class
12.9,
M5
X
20
socket
‐
head
cap
screws
(Yield
Stress
1100
MPa)
shall
be
used
to
replace
the
cover
fasteners.
2.
ISO
Class
12.9,
M5
X
25
socket
‐
head
cap
screws
(Yield
Stress
1100
MPa)
shall
be
used
to
replace
the
base
fasteners.
Fire
Protection
Equipment
Approval
Standards:
FM3260
(2000);
FM3600
(1998);
FM3615
(2006);
ANSI/ISA
60079
‐
0
(2009);
ANSI/ISA
60079
‐
1
(2009);
CAN/CSA
‐
C22.2
No.
60079
‐
0
(2007);
CAN/CSA
‐
C22.2
No.
60079
‐
1
(2007)
Supporting
Standards:
ANSI/FM3260
(2004);
ANSI/NFPA
72
(2002);
ULC/ORD
–
C386
(1990);
CAN/ULC
–
S529
(2002);
CSA
C22.2
No.
0.5
(reaffirmed
1999);
C22.2
No.
32
(reaffirmed
2003);
ANSI/IEC
60529
(2004);
CSA
‐
C22.2
No.
60259
(2005)
ABS
Class
I,
Division
1,
Groups
B,
C
&
D,
T5
Ta
=
‐
40
o
C
to
+85
o
C
(
‐
40
o
F
to
+185
o
F)
IP66
ATEX/
CE
Flameproof
“d”
Ex
d
IIC
T5
Gb
Ta
=
‐
40
o
F
to
+185
o
F
(
‐
40
o
C
to
+85
o
C)
Supporting
Standards:
EN
60079
‐
0:2009;
EN
60079
‐
1:2007
ATEX
Certificate
Number:
FM10ATEX0043X
Specific
Conditions
of
Use:
1.
ISO
Class
A2
‐
70,
M5
X
16
socket
‐
head
cap
screws
(Yield
Stress
450
MPa)
shall
be
used
to
replace
the
cover
fasteners.
2.
ISO
Class
A2
‐
70,
M5
X
16
socket
‐
head
cap
screws
(Yield
Stress
450
MPa)
shall
be
used
to
replace
the
base
fasteners.
3.
Consult
the
manufacturer
if
dimensional
information
on
the
flameproof
joints
is
necessary.
Certificate
of
Conformity:
CE
Mark
for
EMC
(TUV)
CE
Mark
for
ATEX
IP66