IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 10 of 29
Revised 10/21/2013
Analog
Signal
Analog
signal
(4
‐
20
mA)
Signal
level
Detector
State
(±0.1)
mA
Circuit
opening
(2
±
0.1)
mA
Fault
(4
±
0.1)
mA
Normal
(18
±
0.1)
mA
Fire
(2
±
0.1)
mA
Test
Digital
Signal
Informational
digital
signals
are
standard
RS
‐
485
communication
with
Modbus:
Hardware
self
‐
test
Fault
Optical
interference
Fault
Fire
detected
(The
digital
channel
protocol
Modbus
RTU
is
described
in
Appendix
B.)
Relay
Dry
Contact
Signal
Relay
dry
contact
signal:
Operation
of
the
normally
open
Fire
relay
dry
contacts
*
o
FIRE
relay
–
two
‐
directional
single
‐
pole
contact,
which
allows
the
state
to
be
changed
at
the
output
to
normally
closed
or
normally
open
by
using
the
ESP
Commander
program.
The
contact
relay
is
rated
for
currents
ranging
from
10
mA
to
5
A
at
DC
voltage
of
30
V.
The
output
signal
“Fire”
can
be
cleared
after
eliminating
the
source
of
the
alarm
signal.
*
A
normally
closed
condition
of
the
Fire
relay
contacts
does
not
comply
with
the
requirements
of
NFPA
72
or
ULC/ORD
–
C386
and
is
not
approved
by
FM
approvals.
Operation
of
the
normally
open
Fault
relay
dry
contacts
o
FAULT
relay
–
single
‐
direction
pole
contact
which
is
normally
open.
The
relay
is
designed
to
handle
currents
of
10
mA
to
5
A
at
DC
voltage
of
30
V.
Refer
to
Table
4
‐
1:
Determining
LED
Conditions
above.
Operating
Modes
Possible
detector
configurations
using
ESP
Commander
The
IPES–IR/UV
has
the
following
detector
operating
modes:
“Near/far”
and
“slow/fast”
modes
–
To
provide
maximum
sensitivity.
“Latching/non
‐
latching
mode”–
To
select
either
latching
or
non
‐
latching
functionality
of
the
fire
relay,
which
provides
latching
alarm
state
for
the
fire
‐
alarm
relay
in
compliance
with
NFPA
72
and
ULC/ORD
–
C386.
The
manufacturer’s
default
settings
correspond
to
far
and
fast.
To
change
the
manufacturer’s
settings
connect
the
flame
detector
to
the
computer
and
use
the
ESP
Commander
program.