IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 19 of 29
Revised 10/21/2013
8.0 Maintenance
Fire
‐
alarm
and
burglar
‐
fire
alarm
systems
must
be
switched
off
during
testing
to
avoid
operation
of
fire
‐
fighting
equipment.
Maintenance
Activities
IPES
‐
IR/UV
maintenance
includes
the
following
activities:
Visual
examination
Cleaning
Checking
the
grounding
and
explosion
‐
protection
systems
Performance
test.
This
section
describes
maintenance
activities
to
be
performed
once
a
day
or
every
six
months.
Automatic
testing
is
also
discussed.
Daily
Maintenance
Visual
Examination
Perform
a
daily
examination
of
the
IPES
‐
IR/UV,
checking
for
any
visible
mechanical
damage
such
as
dents
to
the
enclosure
or
a
cracked
lens.
If
any
damage
is
noted,
immediately
pull
the
detector
from
service
and
replace
with
a
new
detector.
Every
Six
Months
Every
six
months,
or
as
required,
perform
the
following:
Cleaning
Clean
the
IPES
‐
IR/UV
every
six
months
(if
there
is
no
visible
severe
contamination)
or
as
required
if
the
signal
“Fault”
arises;
also
clean
the
surface
of
the
detector
if
it
is
covered
with
dust.
To
clean
the
detector:
Enclosure
‐
Remove
dust
from
the
enclosure
with
a
brush
or
a
soft
cloth
slightly
wetted
with
denatured
isopropyl
alcohol
(IPA).
After
wiping
the
surface
with
alcohol,
wipe
again
with
a
clean
dry
cloth
to
remove
any
residual
dirt.
Protection
windows
–
Clean
with
a
soft
cloth
wetted
with
denatured
isopropyl
alcohol
(IPA).
After
wiping
the
surface
with
alcohol,
wipe
again
with
a
clean
dry
cloth
to
remove
any
residual
dirt.
Grounding
and
Explosion
‐
Protection
Systems
Check
to
be
sure
that
the
joints
are
sufficiently
tight.
Thoroughly
clean
the
external
grounding
wire
and
apply
anti
‐
seize
lubricant
(supplied
by
the
manufacturer)
on
the
critical
joints
as
referenced
in
Appendix
A1
(Drawing
80033
‐
001).
Perform
this
test
on
all
detectors
in
the
system.
1.
Apply
power
to
the
detector.
After
1
to
5
seconds,
the
output
current
will
increase
to
4
mA,
and
the
indicating
LEDs
will
start
blinking.
2.
If
it
is
necessary
to
isolate
the
detector
fire
relay
from
the
alarm
system,
apply
the
magnetic
collar
over
the
enclosure
as
shown
in
Figure
6
‐
1.
Placing
the
collar
over
the
enclosure
as
shown
allows
the
fire
relay
contacts
to
remain
in
the
non
‐
alarm
state
during
testing.
3.
Perform
the
test
with
the
ITES
Test
Lamp
as
follows: