IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 13 of 29
Revised 10/21/2013
Table
5
‐
1:
Arrangement
of
Electrical
Connections
Arrangement
of
Electrical
Connections
Arrange
the
electrical
connections
as
described
in
Table
5
‐
1,
Table
5
‐
2
and
Figure
5
‐
3
below.
To
connect
the
IPES
‐
IR/UV
to
external
devices,
use
armored
control
cables
4
x
1.5,
which
are
used
in
all
classes
of
explosive
zones
including
indoor
and
outdoor
sites,
channels,
tunnels,
ground
(trenches)
with
corrosive
medium,
and
in
zones
containing
roaming
currents.
Wiring
Requirements
The
temperature
rating
of
all
field
wiring
conductors
shall
be
at
least
10
o
C
greater
than
the
maximum
ambient
temperature
Communications:
14
AWG
(2.08
mm
2)
or
16
AWG
(1.31
mm
2)
shielded
cable,
twisted
pair
is
recommended
to
protect
against
EMI
and
RFI
interference;
Power:
14
AWG
(2.08
mm
2)
or
16
AWG
(1.31
mm
2)
wires.
Ground
wire
shall
be
14
AWG
(2.08
mm
2)
The
wiring
color
and
type
shall
comply
with
local
codes,
ordinances,
and
the
NEC.
It
is
recommended
that
the
local
authority
be
consulted
in
case
of
doubt.
Follow
the
wiring
instructions
in
this
manual
to
ensure
correct
functioning
of
the
detector.
Setting
the
Modbus
Address
and
Baud
Rate
To
ensure
proper
communications,
a
unique
address
must
be
assigned
to
each
device,
as
duplicate
addresses
are
not
automatically
detected.
Modules
with
duplicate
addresses
will
report
with
the
same
address,
confusing
latest
updates.
Record
all
addresses
and
device
types
after
completing
the
installation.
Refer
to
Appendix
B
for
setting
the
Modbus
address
and
baud
rate.
Completing
the
Installation
For
the
following,
refer
to
the
illustrations
in
Appendix
A2
(Drawing
80025
‐
001,
Sheets
1
&
2).
1.
Unscrew
the
M5
Socket
Head
Cap
screws
from
the
base.
Remove
the
detector
from
the
base.
2.
Detach
NPT
conduit
bushing
from
base.
3.
Install
the
base
on
a
suitable
work
platform
and
secure
using
the
4
mounting
screws,
washers,
nuts,
and
rubber
grommets.
4.
Run
the
power,
control,
and
ground
wires
from
the
conduit
into
the
conduit
bushing
and
connect
to
the
wiring
terminals
in
the
base.
Follow
Figure
5
‐
2,
Arrangement
and
Functions
of
Mounting
Connection
Terminals,
for
details.
5.
Tighten
the
conduit
bushing
to
4
‐
1/2
+
‐
1
turns
of
engagement.
Seal
the
conduit
entry
with
an
approved
hazardous
location
conduit
sealant.
6.
Run
the
earth
ground
wire
to
the
external
ground
stud
on
the
base.
7.
After
completing
all
wiring,
refer
to
Table
4
‐
1
to
verify
the
functionality
of
the
front
cover
LEDs.
8.
Inspect
base
and
re
‐
apply
a
thin
film
of
anti
‐
seize
compound
if
required;
re
‐
install
the
detector
on
the
base
and
evenly
tighten
the
M5
screws
to
40
in
‐
lbs.
9.
Upon
completing
the
installation,
check
the
resistance
of
the
earth
ground
lug
to
ground
which
should
not
exceed
1
ohm.