
IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 14 of 29
Revised 10/21/2013
Arrangement
and
Function
of
Mounting
Connection
Terminals
The
arrangement
and
function
of
mounting
connection
terminals
used
to
connect
the
IPES
‐
IR/UV
to
a
control
system
are
shown
below.
Table 5-2: Connecting Terminals
Receptacle
Pin
Function
X3
+24V
24VDC
from
system
power
source
(External
User
Provided)
GND
System
Ground
from
system
power
source
(External
User
Provided)
+4/20
Industry
Standard
+4
‐
20mA
current
loop
output
RS485A
RS
‐
485
MODBUS
RS485B
RS
‐
485
MODBUS
R_WORK
R_WORK
Fault
/
Obstruction
Relay
Normally
Closed
(NC
Type
B)
When
Energized
X4
+24V
Output
to
next
device
if
required
GND
Output
to
next
device
if
required
+4/20
Industry
Standard
+4
‐
20mA
current
loop
output
RS485A
Output
to
next
device
if
required
RS485B
Output
to
next
device
if
required
R_FIRE
R_FIRE
Alarm
Relay
Normally
Open
(NO
Type
A)
When
Energized
X5
Factory
Use
X6
Factory
Use
1)
When
using
an
RS
‐
485
bus
connection,
it
is
advisable
to
connect
the
IPES
‐
IR/UV
to
the
bus
via
the
terminal
box.
To
connect
the
detector
to
the
terminal
box,
use
a
cable
not
longer
than
1.64
feet
(0.5
m).
The
cable
characteristics
should
meet
the
requirement
of
the
cable
entries
mounted
on
the
IPES
‐
IR/UV
casing
and
those
of
the
terminal
box.
2)
Arrange
the
power
‐
supply
system
so
that
the
power
‐
supply
voltage
across
the
device
terminals
ranges
from
18
to
32
V
(taking
into
account
the
IPES
‐
IR/UV
consumption).
Figure 5-2: Arrangement and Functions of Mounting Connection Terminals
Summary of Contents for IPES-IR/UV
Page 1: ...IPES IR UV Flame Detector Operating Manual 80010 001 R07 ...
Page 2: ......
Page 6: ......