IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 17 of 29
Revised 10/21/2013
Procedure
Perform
this
test
on
all
detectors
in
the
system.
1.
Apply
power
to
the
detector.
After
1
to
5
seconds,
the
output
current
will
increase
to
4
mA,
and
the
indicating
LEDs
will
start
blinking.
2.
If
it
is
necessary
to
isolate
the
detector
fire
relay
from
the
alarm
system,
apply
the
magnetic
collar
over
the
enclosure
with
the
tab
on
the
bracelet
fitting
into
the
alignment
notch
as
shown
in
Figure
6
‐
1.
Placing
the
collar
over
the
enclosure
as
shown
allows
the
fire
relay
contacts
to
remain
in
the
non
‐
alarm
state
during
testing.
3.
Perform
the
test
with
the
ITES
Test
Lamp
as
follows:
a)
Position
the
Test
Lamp
at
a
distance
of
0.5
to
1
meters
from
the
front
cover
of
the
detector.
b)
Turn
the
Test
Lamp
on
and
adjust
the
beam
of
light
so
it
covers
the
front
cover
of
the
detector.
c)
The
detector’s
front
red
indicator
LED
will
light,
confirming
detection.
If
the
Test
Lamp
is
turned
off,
the
red
indicator
will
stay
lit
for
up
to
10
seconds,
depending
on
the
detector’s
internal
switch
configuration.
d)
The
Test
Lamp
can
be
used
to
verify
the
field
of
view
of
the
detector
up
to
a
distance
of
2
meters
away.
4.
If
any
detector
fails
this
test,
refer
to
Section
7.0,
Troubleshooting.
5.
Once
testing
is
complete,
remove
the
magnetic
collar
before
reconnecting
the
detector
to
the
fire
‐
alarm
or
burglar
‐
fire
alarm
system.
NOTES:
Always
make
sure
that
the
Test
Lamp
has
fresh
batteries.
Keep
the
Test
Lamp
lens
free
from
dust,
dirt,
and
moisture.
If
necessary,
clean
the
lens
with
a
soft
wool
or
cotton
cloth.