IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 6 of 29
Revised 10/21/2013
False
Stimuli
Exposure
When
the
IPES
‐
IR/UV
is
exposed
to
the
fires
specified
above,
and
are
in
the
presence
of
the
following
false
stimuli
sources
–
modulated
at
approximately
1.5
Hz,
and
un
‐
modulated
–
no
false
alarm
activation
or
instability
occurs
at
the
minimum
distances
listed
below.
Source
Distance
Heater
12
inches
(30.48
cm.)
Arc
welder
9.8
feet
(3
m.)
Fluorescent
6
inches
(15.24
cm.)
Halogen
6
inches
(15.24
cm.)
Incandescent
6
inches
(15.24
cm.)
Direct
sunlight
Detectors
not
affected
by
frequency
range
of
visible
light
Indirect
sunlight
Detectors
not
affected
by
frequency
range
of
visible
light
Field
of
View
The
IPES
‐
IR/UV’s
viewing
angle
is
varied
from
the
center
line
up,
down,
left
and
right.
The
detector
is
exposed
to
each
of
the
test
fires
described
in
“Flame
Response
Sensitivity”
above
at
a
distance
described
in
the
table
below.
Fuel
Horizontal
(Left)
Horizontal
(Right)
Vertical
(Up)
Vertical
(Down)
Min,
Distance
Avg.
Time
n
‐
Heptane
45
o
45
o
45
o
45
o
56.1
ft.
(17.1
m.)
4.61
sec.
Denatured
ethyl
alcohol
85.4%
45
o
45
o
45
o
45
o
41
ft.
(12.5
m.)
4.55
sec.
JP4
45
o
45
o
45
o
45
o
82
ft.
(25
m.)
Instantaneously
4.0
Performance
Characteristics
Appearance
The
IPES
‐
IR/UV
consists
of
an
explosion
‐
proof
casing
containing
sensors
which
convert
Earth
Ground
Attachment
Point
Mounting
Base
Optical
Window
with
IR
&
UV
Detectors
&
Operational
Status
LEDs
Front
Cover
Rear
Cover
(remove
for
wire
installation)
Figure 4-1: Appearance of the IPES-IR/UV
Tilt
&
Pan
Swivel
Adjustments