IPES-IR/UV Flame Detector
80010-001 R07
Operating Manual
Page 12 of 29
Revised 10/21/2013
vibrations
(see
Appendix
A
‐
2,
Drawing
80025
‐
001,
Sheet
1).
Note:
ESP
Safety
Inc.
recommends
bolting
the
mounting
base
plate
to
the
mounting
surface.
If
bolting
is
not
possible,
the
mounting
plate
can
be
welded
to
the
mounting
surface
if
it
is
a
similar
metal
(either
316
Stainless
Steel
or
6061
aluminum).
Before
welding,
be
sure
to
remove
the
detector
from
the
base
plate
before
attempting
any
weld
operation.
Moisture
Damage
Protection
It
is
the
responsibility
of
the
installer
to
take
proper
precautions
during
installation
to
protect
the
electrical
connections
and
components
from
moisture.
Anti
‐
seize
lubricant
is
provided
for
easy
assembly
and
corrosion
protection
of
the
joints
between
the
enclosure/cover
and
enclosure/base.
After
disassembly,
wipe
these
surfaces
clean
with
a
soft
cotton
or
wool
cloth
and
then
re
‐
apply
a
thin
layer
of
lubricant
prior
to
assembly.
See
Appendix
A2
(Drawing
80025
‐
001,
Sheet
1).
If
installing
wiring
cable
in
conduit,
do
not
use
conduit
for
wiring
to
other
equipment.
Care
should
be
taken
to
not
install
the
detector
where
heavy
condensate,
rain,
or
fog
can
cover
the
lens
and
reduce
the
sensitivity
of
the
detector.
If
possible,
conduct
fire
tests
to
confirm
detection.
Caution:
All
cable/conduit
entries
must
be
sealed
with
an
appropriate
and
certified
sealing
plug
and
cable
gland.
The
use
of
industrial
grade,
armored
field
cable
is
recommended.
Figure 5-1: View of IPES-IR/UV with Base Removed