RS-485 connection to SYSTEM 500M/1000M

Connect the RS-485 cable to socket 1-13 (refer to figure 1):

SYSTEM 500M/1000M

Keyboard 580M/1801M/1802M

Pin

Description

Pin

Description

6 or 8 Positive signal

6 or 8 Positive signal

7 or 9 Negative signal

7 or 9 Negative signal

1, 4 or 5* GND (Connect to cable screen)

1, 4 or 5* GND (Connect to cable screen)

Remember to terminate the RS-485 line in both ends of the cable. This is done by setting the
belonging small switches to the 120 

Ω 

or 100 

Ω 

position corresponding to the characteristic

impedance of the cable used, refer to fig. 1-14. Make sure, that only the first and the last
physical unit on the cable is terminated, refer to figure 2 for termination instructions. On all
other units the termination switches should be set to the OFF position.

Maximum cable length is 1200 metres.

It is recommended to use high quality twisted pair cable designed for data transmission.
*Connection of cable shield/screen is optional and will normally not be needed.

RS-485 connection to telemetry receivers Series BDR-500, the ICU and BED-108

Connect the RS-485 cable to socket 1-13 (refer to figure 1):

Series 1500

BDR-550/1

BDR-510/4

BDR-511/2/3

BDR-575

ICU

BED-108

Pin

Desc.

Pin

Desc.

Pin

Desc.

Pin

Desc.

Pin

Desc.

Pin

Desc.

Pin

Desc.

6 or 8 Pos.

*X5- PCM IN-

X7+ CTRL IN+ X12+ PCM IN+

2

N/A

1

COM+ X3+ ERNA+

7 or 9 Neg.

*X5+ PCM IN+ X7-

CTRL IN-

X12-

PCM IN-

1

N/A

2

COM-

X3- ERNA-

1, 4, 5 GND

Do NOT connect!

Details on interconnecting various types of telemetry receivers and termination of the RS-485
line can be found on figure 3.

Telemetry Receivers Series BDR-51X and BDR-55X and the BED-108 Control Signal Distributor
Unit will terminate the RS-485 properly by themselves when installed in the correct daisy chain
configuration and do not require additional line termination. The ICU and the BDR-575 are
bus-connected and consequently the line must be terminated, on the ICU with an external
resistor, on the BDR-575 by enabling the RS-485 LK1 jumper on the interface board. 

Different types of telemetry receivers can also be mixed on the common control line.

Remember, that each telemetry receiver/ICU must have an unique address equal to the camera
number minus 1, refer to the relevant telemetry receiver manual. Also the Series 1500
keyboard must be set for direct control of telemetry receivers (

CamCrtl

), refer to the 

Set-up

section located later in this manual.

Maximum cable length is 1200 metres. However, telemetry receivers Series BDR-51X and
BDR-55X as well as the BED-108 features an active control signal repeater allowing further
3000 meters (BDR-51X further 1200 meters) distance to the next unit.

Installation and Setup instruction for Keyboard Series 1500

Page 4

Summary of Contents for 1500M

Page 1: ...OFFICE ERNITEC FRANCE PARC PEREIRE 95 RUE PEREIRE BAT D 78100 SAINT GERMAINE EN LAYE FRANCE TELEPHONE 1 39 21 12 00 TELEFAX 1 39 21 12 95 E MAIL ernitec fr magic fr GERMAN OFFICE ERNITEC GmbH STORMARNRING 28 22145 STAPELFELD GERMANY TELEPHONE 040 67 56 25 0 TELEFAX 040 67 56 25 25 E MAIL ernitec aol com JAPAN OFFICE ERNITEC JAPAN LTD 8 16 GAKUEN HIGASHIMACHI 1 CHOME KODAIRA SHI TOKYO 187 0043 JAPA...

Page 2: ...ed with keyboard 1501M or 1503M Keyboard types Keyboard 1500M is equipped with a serial port with selectable RS 232 RS 485 interface Keyboard 1501M is furthermore equipped with a joystick for variable speed operation of BDR 575 and the ICU Keyboard 1502M is equipped with a serial port with selectable RS 232 RS 485 interface and an ARC net port for connection to SYSTEM 500M and 1000M A LCD display ...

Page 3: ... 6 or 9 Negative signal 6 or 9 Negative signal All SYSTEM 1000M units are interconnected through the ARC net Also the keyboards might be connected to the ARC net Remember to terminate the ARC net line in both ends of the cable This is done by setting the belonging small switches to the 120 Ω or 100 Ω position corresponding to the characteristic impedance of the cable used refer to fig 1 12 Make su...

Page 4: ...n Desc Pin Desc 6 or 8 Pos X5 PCM IN X7 CTRL IN X12 PCM IN 2 N A 1 COM X3 ERNA 7 or 9 Neg X5 PCM IN X7 CTRL IN X12 PCM IN 1 N A 2 COM X3 ERNA 1 4 5 GND Do NOT connect Details on interconnecting various types of telemetry receivers and termination of the RS 485 line can be found on figure 3 Telemetry Receivers Series BDR 51X and BDR 55X and the BED 108 Control Signal Distributor Unit will terminate...

Page 5: ...oards having the same address When used as a matrix keyboard make sure the following parameters are set correct Keyboard type SysKbd System keyboard Communication media In accordance with the interface used Baud rate In accordance with baud rate set in SYSTEM 500M 1000M Keyboard address Make sure the address set is unique When used for direct control of telemetry receivers ICU s Keyboard type CamC...

Page 6: ...et up procedure Change the keyboard type Press the key 1 to change the keyboard type Press 1 to set the keyboard for Direct Camera Control press 2 to set the keyboard for System Control Change of keyboard address Press the key 2 to change the keyboard address press a number between 3 and 6 indicating the new keyboard address Change the baud rate Press the key 3 to change the baud rate setting Pres...

Page 7: ...Press the key 9 to change the password and enter the new password 4 digits Re enter the new password Installation and Setup instruction for Keyboard Series 1500 Page 7 ...

Page 8: ...word Re enter new password Setup is finished Direct Camera control 1 1 2 System keyboard Keyboard No 3 2 3 4 5 6 Keyboard No 4 Keyboard No 5 Keyboard No 6 4 9600 Baud 1200 Baud 3 1 2 3 2400 Baud 4800 Baud RS232 4 1 2 RS485 Aux latch 5 1 2 3 Beep HIGH Beep LOW 9 2 3 1 4 2 3 1 4 5 19200 Baud 2 Aux Nolatch Beep OFF 6 1 Default factory settings 6 38400 Baud 3 Aux 1801M Joystick calibrated 7 CLR ESC In...

Page 9: ...the valid baud rates Change of keyboard address Press the F9 key to get to the Kdb No menu Press the F4 key to toggle between the valid keyboard numbers Set the function of the AUX keys Press the F9 key to get to the AUX menu Press the F6 key to toggle between Latch No Latch 1801M function Change the password Press the F9 key to get to the Change Password menu Press F7 and enter the new password 4...

Page 10: ... Set Function of AUX relays in BDR 5XX ICU Change password Service menu only Enter Password XXXX F4 OpMode F6 Comm F7 Baud F9 XXXXXX XXXX XXXX More F4 Kbd No F6 AUX F7 Change F9 X XX XXXX Password More Enter Password XXXX Reenter Password XXXX F4 ArcNet F6 Error F7 S W F9 Stat Log Ver More F4 Beep F6 Reset F7 Test F9 XXXX Settings Joystick More Set beeper tone Reset keyboard settings to default ma...

Page 11: ...tions are now directed to camera 3 address 2 until a new camera is selected Select all cameras broadcast If all cameras should be operated simulteneously press Broadcast commands Warning When e g activating the pan functions all cameras will pan The broadcast function should therefore be used with care Zoom Change the focal length 1500M 1502M 1501M 1503M 1500M 1502M 1501M 1503M Zoom wide Zoom narr...

Page 12: ...500M 1502M 1501M 1503M Tilt up Tilt down JOYSTICK NOTE When controlling a variable speed Pan tilt BDR 575 or ICU pushing the joystick towards its extremes will increase speed Activating an AUX relay To activate AUX relay 2 press 2 ð ð AUX Activate AUX 2 relay Note If the Keyboard 1500 is set for No Latch operation the relay is automatically de activated when the AUX key is released If set for Latc...

Page 13: ...s press Start sequence The sequence of pre positions is automatically aborted when another function is operated Remove insert text Series BDR 550 only Remove insert the text generated by the currently controlled telemetry receiver 150XM Remove or Insert text from telemetry receiver Auto focus ICU only In order to switch to auto focus press AUTO ð ð or AUTO ð ð Enable auto focus Auto iris ICU only ...

Page 14: ...controlled ESC ð AUX Display preposition sequence stack Insert a preposition in the sequence stack To insert preposition number 1 in the sequence stack stored in the telemetry receiver 1 ð ð ESC ð ð VCR 1 1 ð ð SHIFT INS 1500M 1502M 1501M 1503M Insert preposition number 1 in the sequence stack Delete a preposition from the sequence stack To delete preposition number 1 from the sequence stack store...

Page 15: ... ð 6 ð ð Use pre position 8 as Homeposition with a 60 sec time out Note that the time out entry automatically is multiplied with 10 Max time out entry is 255 corresponding to 2550 seconds Set Auto panning limits available on the ICU BDR 575 only To set the two limit positions for auto panning for the camera being controlled 1 ð ð SHIFT AUTO 2 ð ð SHIFT AUTO 1501M 1503M only 1501M 1503M only Set au...

Reviews: