Appendix F DNP3 Communication Protocol
D02416R04.00
F-PRO 5100 User Manual
Appendix F-9
Name
Point
Index
Units
Scale
Change
Event Class
Deadband
Main Va-Mag
0
kV
10
2
2% nominal
Main Va-Ang
1
degrees
10
2
0.5 degrees
Main Vb-Mag
2
kV
10
2
2% nominal
Main Vb-Ang
3
degrees
10
2
0.5 degrees
Main Vc-Mag
4
kV
10
2
2% nominal
Main Vc-Ang
5
degrees
10
2
0.5 degrees
Main Ia-Mag
6
A
1
2
2% nominal
Main Ia-Ang
7
degrees
10
2
0.5 degrees
Main Ib-Mag
8
A
1
2
2% nominal
Main Ib-Ang
9
degrees
10
2
0.5 degrees
Main Ic-Mag
10
A
1
2
2% nominal
Main Ic-Ang
11
degrees
10
2
0.5 degrees
Aux Ia-Mag
12
A
1
2
2% nominal
Aux Ia-Ang
13
degrees
10
2
0.5 degrees
Aux Ib-Mag
14
A
1
2
2% nominal
Aux Ib-Ang
15
degrees
10
2
0.5 degrees
Aux Ic-Mag
16
A
1
2
2% nominal
Aux Ic-Ang
17
degrees
10
2
0.5 degrees
Line Ia-Mag
18
A
1
2
2% nominal
Line Ia-Ang
19
degrees
10
2
0.5 degrees
Line Ib-Mag
20
A
1
2
2% nominal
Line Ib-Ang
21
degrees
10
2
0.5 degrees
Line Ic-Mag
22
A
1
2
2% nominal
Line Ic-Ang
23
degrees
10
2
0.5 degrees
Sync V-Mag
24
kV
10
2
2% nominal
Sync V-Ang
25
degrees
10
2
0.5 degrees
Real Power (P)
26
MW
10
2
4% nominal
Reactive Power (Q)
27
MVAR
10
2
4% nominal
Pos Seq Voltage
28
kV
10
2
2% nominal
Pos Seq Current
29
A
1
2
2% nominal
Frequency
30
Hz
100
2
0.05 Hz
THD
31
%
100
2
0.25%
Active Setting Group Number
32
1
2
1
Demand Real Power Out
33
MW
10
2
0.5
Demand Real Power In
34
MW
10
2
0.5
Demand Reactive Power Out
35
MVAR
10
2
0.5
Summary of Contents for F-PRO 5100
Page 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 28: ......
Page 94: ......
Page 98: ......
Page 140: ......
Page 146: ......
Page 168: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 190: ......