D02416R04.00
F-PRO 5100 User Manual
Appendix B-9
Pickup Delay
2.00
seconds
0.00 to 99.99
32Q
Enabled
Pickup
3.00
amperes
[-15.00, -0.25]
or [0.25, 15.00]
Pickup Delay
2.00
seconds
0.00 to 99.99
21P - Phase Distance
21P-1
Enabled
Forward Reach
10.00
ohms
0.05 to 66.00
Delta Current Supervision
0.2
amperes
0.2 to 50.0
21P-2
Enabled
Forward Reach
10.00
ohms
0.05 to 66.00
Delta Current Supervision
0.2
amperes
0.2 to 50.0
THD - Total Harmonic Distortion
THD
Enabled
Pickup
10.0
%
5.0 to 100.0
Demand Metering
Demand Metering
Disabled
Demand Interval
5
minutes
5 to 60
Demand Meter Type
Integrating
I*I*t
I*I*t Main
Disabled
External Input or ProLogic for Trip
<disabled>
I*I*t Limit
99999.0
(kA)^2*s
0.1 to 99999.0
I*I*t Aux
Disabled
External Input or ProLogic for Trip
<disabled>
I*I*t Limit
99999.0
(kA)^2*s
0.1 to 99999.0
PL 1 [ProLogic 1]
ProLogic 1
Disabled
Target
Enabled
Pickup Delay
0.00
seconds
0.00 to 999.00
Dropout Delay
0.00
seconds
0.00 to 999.00
Operator 1
Input A
<Unused = 0>
Operator 2
Input B
<Unused = 0>
Operator 3
Input C
<Unused = 0>
Operator 4
Input D
<Unused = 0>
F-PRO Settings Summary - Setting Group 1 [Setting Group 1]
Name
Symbol/Value
Unit
Range
Summary of Contents for F-PRO 5100
Page 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 28: ......
Page 94: ......
Page 98: ......
Page 140: ......
Page 146: ......
Page 168: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 190: ......