D02416R04.00
F-PRO 5100 User Manual
Appendix B-7
Initiate Fault Location
Disabled
ProLogic Control
Disabled
25/27/59 - Sync Check
25 Sync Check
Enabled
Maximum Voltage
70.0
volts
60.0 to 138.0
Minimum Voltage
60.0
volts
40.0 to 69.9
Angle Difference
20.0
degrees
1.0 to 50.0
Pickup Delay
0.02
seconds
0.00 to 99.99
Dead Main Live Sync (DMLS)
Enabled
Live Main Dead Sync (LMDS)
Enabled
Dead Main Dead Sync (DMDS)
Enabled
79 - Recloser
Main
Enabled
Number of Shots
4
First Reclose (T1)
1.00
seconds
0.02 to 99.99
Second Reclose (T2)
5.00
seconds
1.00 to 99.99
Third Reclose (T3)
10.00
seconds
1.00 to 99.99
Fourth Reclose (T4)
20.00
seconds
1.00 to 99.99
Close Time (Tp)
0.20
seconds
0.01 to 1.00
Lockout Reset (Td)
25.00
seconds
0.00 to 99.99
Initiate Reset (TDI)
1.00
seconds
0.00 to 99.99
Block Reset (TDB)
0.50
seconds
0.00 to 99.99
Sync Control
Disabled
Aux
Enabled
Number of Shots
4
First Reclose (T1)
1.00
seconds
0.02 to 99.99
Second Reclose (T2)
5.00
seconds
1.00 to 99.99
Third Reclose (T3)
10.00
seconds
1.00 to 99.99
Fourth Reclose (T4)
20.00
seconds
1.00 to 99.99
Close Time (Tp)
0.20
seconds
0.01 to 1.00
Lockout Reset (Td)
25.00
seconds
0.00 to 99.99
Initiate Reset (TDI)
1.00
seconds
0.00 to 99.99
Block Reset (TDB)
0.50
seconds
0.00 to 99.99
Sync Control
Disabled
59 - Overvoltage
59-1
Enabled
Gate Switch
OR
Pickup
70.0
volts
1.0 to 138.0
F-PRO Settings Summary - Setting Group 1 [Setting Group 1]
Name
Symbol/Value
Unit
Range
Summary of Contents for F-PRO 5100
Page 1: ...F PRO Feeder Protection Relay Model 5100 User Manual Version 4 0 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 28: ......
Page 94: ......
Page 98: ......
Page 140: ......
Page 146: ......
Page 168: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 190: ......