© The Entryphone Company Limited
7
Connection Diagrams
Notes
.
The diagram shows examples of the PinNet lock release switching outputs connected to the three
most common door release types:
1.
Fail secure release. Power is applied to the device to release the lock.
2.
Fail unlock release. The device is continuously powered to keep it locked.
3.
Maglock. The device is continuously powered to keep it locked.
With maglocks there is no mechanical means to open the door (unlike door releases that
operate in conjunction with standard night latch locks which can be operated using the handle
on the inside and a key from the outside) and therefore a request-to-exit (RTE) must be
provided for egress and an emergency break-glass unit is also
required for fire regulation
compliance.
The diagram shows each device powered by its own power supply (PSU). If required the locks can be
powered through the unit via the “LOCKS” terminals (please note there are jumper links on the board
so individual lock outputs can be isolated).