POWER FACTOR CONTROLLER
RG3-12C/CS
8
3.4 Selection of Proper Switching Sequence
RG312C/CS has 10 different program modes which determines
the power ratio sequence of the capacitor steps.
The switching programs are given in the table.
If the step sequence is selected as in program 02(PS-02), many
identical connection components must be used. When a step
sequence between the 3rd and the 8th one is selected, less
identical connection components will be used. By selecting the
9th connection sequence, different group powers can be achieved.
In this sequence connection, the rating of each capacitor step
value may exceed that of the first by a maximum amount equal
to the preceding capacitor steps value. By using this setting,
less capacitors will be used. When the 10th connection sequence
is selected, RG3-12C/CS will calculate the capacitor step power
values automatically. RG3-12C/CS counts swithing on&off times
of all capacitor steps and so only the most necessary step is
switched on. Thus, maximum service life time of the system
is ensured.
Note: In the 10th program(PS-10), power values and connection
types(except the first step) of the single phase capacitor
steps(r, s, t, rst, oFF) can be set by user. In Auto setup mode
power values of all capacitor steps are measured and
connection types of the capacitor steps are detected by the
device. In all the connection sequences except the 10th one,
only the 1st capacitor step power can be set. All the other
capacitor step values are calculated according to the 1st
capacitor steps power value.
Set the program option suitable for your system in this menu.
Using the
UP/DOWN
buttons, select the Program
(Prog)
menu.
When program menu is displayed, program LED turns on.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
Press the
SET
button to select the switching program.
Enter the desired program number between 01-10 and press the
SET
button.
Using the
UP/DOWN
buttons, enter to another menu option
which you wish to change. If you are not going to change any
more settings, press the
ESC
button.
P R O G R A M
S E Q U E N C E
01
02
03
04
05
06
07
08
09
*10
linear
1.1.1.1................
1.1.2.2................
1.2.2.2................
1.2.3.3................
1.2.4.4.................
1.1.2.4................
1.2.3.4................
1.2.4.8................
Capacitor step values are calculated automatically.
* Recommended switching program.
In order to decrease harmful effects of instant reactive power loads to the
relays and capacitors, delay time (in terms of seconds) for capacitor steps
is entered in this menu.
Switch-on delay time must be set according to system requirement in
order to achieve compensation targets and also to provide long life time
for contactors and capacitors.
3.5.a Switch-On Delay Time Setting
Note: t-on and t-of time periods must be set according to your systems
requirements. If t-on time is set very long, relay can not switch on until
the end of this time period and so target compensation ratios may not
be achieved. If t-on time is set too short, capacitor steps switch on&off
frequently in case of fast load variations and this will shorten the life
time of contactors and capacitors. For this reason, it is very important
to set these time periods according to your systems requirement.
Using the
UP/DOWN
buttons, select the delay time menu
(dELy)
.
When delay time menu is displayed, time LED turns on.
Press the
SET
button for 3 sec. in order to enter to the
3.5 Switching On&Off and Discharge Time Settings
Press
SET
button for 3 sec. in order to enter to the menu.
3 sec.
3 sec.