POWER FACTOR CONTROLLER
RG3-12C/CS
18
In this menu; the upper temperature limit, which activates the overheating
protection, is programmed between 00.0-99.9 °C(Refer to Technical
Features section for measurable ranges).
3.9.c.a Programming the Upper Limit of Temperature Alarm
Note : Temperature measurement feature is optional for RG3-12CS.
In order to protect the capacitors from overheating, upper (HEAt SP-H) and
lower (HEAt SP-L) limits between 00.0-99.9 °C and step protection (HEAt
StEP) are all set in this menu. If the temperature exceeds the upper limit,
which is programmed in the device, for 10 seconds; RG3-12C/CS gives
an alarm signal (Erro r-10) and switches off or does nothing for the capacitor
steps according to selected capacitor step setting(HEAt STEP). After the
temperature stays under the lower limit value for 10 seconds, the alarm
state disappears.
3.9.c Temperature Alarm Settings
SAUE
If you want to leave the setup menu without making any other changes,
press the
ESC
button until
SAVE SEt yES
shows on the screen. If
you want to save the changes, press the
SET
button. If not, press the
ESC
button.
Press the
SET
button to enter the alarm(ALr) settings.
Using the
UP/DOWN
buttons, find temperature alarm menu(HEAT) which
is the second setting in the alarm menu.
Press the
SET
button to enter the upper limit of the temperature
value(SP-H).
Press the
SET
button to select the SP-H menu in which the upper and
lower limits for the temperature alarm to activate or deactivate the alarm
relay is programmed.
Enter a value between 00.0-99.9 °C and press the
SET
button. If you
are going to change another setting, return to the menu by pressing the
SET
button. If you do not want to set another parameter, press the
ESC
button.
SAUE
If you want to leave the setup menu without making any other changes,
press the
ESC
button until
SAVE SEt yES
shows on the screen. If
you want to save the changes, press the
SET
button. If not, press the
ESC
button.
Using the
UP/DOWN
buttons, find the alarm menu(ALr). When Alarm
menu is selected, alarm LED turns on.
Press the
SET
button for 3 sec. in order to enter to the
menu.
3 sec.