If you want to leave the setup menu without making any other changes,
press the
ESC
button until
SAVE SEt yES
shows on the screen. If
you want to save the changes, press the
SET
button. If not, press the
ESC
button.
POWER FACTOR CONTROLLER
RG3-12C/CS
21
3.9.d.c Programming the Switching Off of the Capacitor
Steps in Case of Harmonic Alarm
In order to protect the capacitors from overvoltage harmonic, they can be
set to switch off in case of a harmonic alarm in this menu.
If
on
option is selected, when overvoltage harmonic error occurs,
capacitor steps stay switched on.
If
of
option is selected, when overvoltage harmonic error occurs, capacitor
steps switch off.
SAUE
If you want to leave the setup menu without making any other changes,
press the
ESC
button until
SAVE SEt yES
shows on the screen. If
you want to save the changes, press the
SET
button. If not, press the
ESC
button.
SAUE
Enter the delay time for overvoltage harmonic between 0-999,9 seconds
and press
SET
button.
Using the
UP/DOWN
buttons, find capacitor step(StEP) menu.
Press the
SET
button for capacitor step menu which is the third setting
in the harmonic menu.
Using the
UP/DOWN
buttons, select
on
(capacitors stay switched on)
or
of
(capacitors switch off) option and press
SET
button. If you are
going to change another setting, return to the menu by pressing the
SET
button. If you do not want to set another parameter, press the
ESC
button.
The values for switching on and switching off are entered in this menu.
There are two submenus as FAn on and FAn oFF in this menu.
Note: Temperature measurement feature for RG3-12C/CS is optional.
3.10 Fan Relay Settings
3.10.a Switch On Value for Fan Relay
Fan relay switching on temperature is programmed in this menu. Relay is
switched on after 10 sec. when the measured temperature increase the
set value and Fan led light will be on.
First setting of the fan relay menu is is the operating temperature of the
fan. Press
SET
button to enter this menu.
Press the
SET
button for 3 sec. in order to enter to the
menu.
3 sec.
Using the
UP/DOWN
buttons, find fan relay settings(FAn) menu.