Entes RG3-12C Manual Download Page 13

POWER FACTOR CONTROLLER

RG3-12C/CS

12

2

SAUE

If you want to leave the setup menu without making any other changes,
press the 

“ESC”

 button until 

“SAVE SEt yES”

 shows on the screen. If

you want to save the changes, press the 

“SET”

 button. If not, press the

“ESC”

 button.

Enter the power value of the second capacitor step and then press the

“SET”

 button. If you do not want to set another parameter, press the 

“ESC”

button.

CAP C-03

In this menu, capacitor setting for third step are done.

CAP C-04

In this menu, capacitor setting for fourth step are done.

CAP C-05

In this menu, capacitor setting for fifth step are done.

CAP C-06

In this menu, capacitor setting for sixth step are done.

CAP C-07

In this menu, capacitor setting for seventh step are done.

CAP C-08

In this menu, capacitor setting for eighth step are done.

CAP C-09

In this menu, capacitor setting for nineth step are done.

CAP C-10

In this menu, capacitor setting for tenth step are done.

CAP C-11

In this menu, capacitor setting for eleventh step are done.

CAP C-12

In this menu, capacitor setting for twelveth step are done.

    Above capacitor steps’ settings are done just like second capacitor step
setting (C-02).

In this menu, current transformer ratio can be set between 1-2000.

For example :

 For a 150/5 current transformer, CT ratio must be set as

30.

Note : Be aware that this value is entered as a ratio, not CT primary

or secondary value.

3.7.a Current Transformer Ratio Setting

To obtain accurate power values when calculating the capacitor step
powers, current and voltage transformer ratios must be entered correctly.
If these ratios are entered incorrectly, the calculated capacitor step powers
will be incorrect. When these ratios aren’t entered, the device will set these
ratios as  

“1”

 and capacitor step powers will be calculated according to

this setting.
Current and voltage transformer ratios can be set separately.

Using the 

“UP/DOWN”

 buttons, find current and voltage transformer ratio

menu (trF). When this menu is selected, Transformer (VA/TRF) LED turns
on.

Press the 

“SET”

 button to enter to the CT and VT ratio setting menu.

Enter CT ratio between 1-2000 and press the 

“SET”

 button. 

If you do not want

to set another parameter, press the 

“ESC”

 button.

SAUE

If you want to leave the setup menu without making any other changes,
press the 

“ESC”

 button until 

“SAVE SEt yES”

 shows on the screen. If

you want to save the changes, press the 

“SET”

 button. If not, press the

“ESC”

 button.

3.7 Current and Voltage Transformer Ratio Settings

Press the 

“SET”

 button for 3 sec. in order to enter to the menu.

3 sec.

The first setting in the CT and VT ratio menu is the CT ratio menu.
Press the 

“SET”

 button to set CT ratio.

Summary of Contents for RG3-12C

Page 1: ...scharge Time Settings 8 3 6 Power Value and Connection Type Settings for Capacitors 10 3 7 Current and Voltage Transformer Ratio Settings 12 3 8 Reset Settings 14 3 9 Alarm Settings 15 3 10 Fan Relay...

Page 2: ...current transformer terminals If you disconnect them be sure to short circuit the terminals or connect them to another parallel load which has a low impedance Otherwise dangerously high voltage at th...

Page 3: ...f the reactive loads became a necessity in todays energy network Power factor controllers monitor the reactive power of a plant and try to match the power factor value which is defined as the ratio of...

Page 4: ...NORMAL LED 24 C LED 25 26 27 28 29 30 31 32 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on t...

Page 5: ...corrects the errors and then calculates the capacitor values After connection errors are corrected capacitor steps are calculated with turning ON the Auto Setup function in Auto menu Refer to Automat...

Page 6: ...can be monitored from the 12 step LEDs on the front panel C LED lights up when a step is switching on and C LED lights up when a step is switching off Factory set values for switching on t on and swi...

Page 7: ...ic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be checked Select on or of using the UP and DOWN buttons Select on for...

Page 8: ...sj values as Cosj ve Cosj2 If there is a voltage between 110 250 VAC present on the generator inputs of the device the target Cosj set on the device is deactivated and target Cosj2 is activated Then t...

Page 9: ...program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET...

Page 10: ...f you want to save the changes press the SET button If not press the ESC button Switch off delay time must be set according to system requirement in order to achieve compensation targets and also to p...

Page 11: ...s power values are calculated according to selected program When setup parameter is selected as of power values of all capacitor steps including first capacitor step can be set manually Note When setu...

Page 12: ...SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value settings of al...

Page 13: ...000 For example For a 150 5 current transformer CT ratio must be set as 30 Note Be aware that this value is entered as a ratio not CT primary or secondary value 3 7 a Current Transformer Ratio Setting...

Page 14: ...indicated in the table in order to select reactive power calculation methode for mechanical and digital energymeters Using the UP DOWN buttons find the reactive energy calculation method menu CALC Pr...

Page 15: ...turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Using the UP DOWN buttons selec...

Page 16: ...rvoltage Alarm Setting 3 9 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 9 a a Overvoltage Setting SAUE If you wa...

Page 17: ...nds If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button The third setting in the voltage menu UoLt...

Page 18: ...he ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Page 19: ...ther changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button Press the SET button to enter the alarm ALr se...

Page 20: ...0 0 99 9 C and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button SAUE If yo...

Page 21: ...ress the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over voltage harmonic menu tHd which is the fourth setting in the alarm menu In this menu over voltage harmonic value...

Page 22: ...999 9 seconds and press SET button Using the UP DOWN buttons find capacitor step StEP menu Press the SET button for capacitor step menu which is the third setting in the harmonic menu Using the UP DOW...

Page 23: ...programmed in this menu The first parameter in the Fan menu FAn is the operating temperature of the fan Press SET button to enter the operating temperature settings Press the SET button to program th...

Page 24: ...both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the generator input 3 11 Resetting the Energy Counters and Entering the Ene...

Page 25: ...he energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gEn ACt yES parameter is s...

Page 26: ...change another setting return to the menu by pressing the SET button If you do not want to set another parameter press the ESC button In this menu Parity value can be set as no odd or EVEn 3 11 c Par...

Page 27: ...SET button If you do not want to set another parameter press the ESC button In this menu user password is activated When the password is activated a pin code is always required before entering to the...

Page 28: ...you do not want to set another parameter press the ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If y...

Page 29: ...n Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displayed on...

Page 30: ...by using UP DOWN buttons when I LED lights When phase current values are displayed if SET button is pressed HAR LED lights odd numbered harmonic values up to 19th harmonic can be observed In the meas...

Page 31: ...ues are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on t...

Page 32: ...ng UP DOWN buttons when W and h LEDs light In the example below I indicates that the displayed parameter is import energy and the remaining numbers show the energy value such as 203385706 8 kWh While...

Page 33: ...ncreased Compensation Error Compensation Error Overheating Defected capacitor step or variable loads Target Cosj is capacitive even if all capacitor steps are switched off Capacitor powers are not suf...

Page 34: ...g int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10 11 1...

Page 35: ...06F 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE...

Page 36: ...126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 PHASE 1 VOLTAGE 13TH HARMONIC P...

Page 37: ...C 800D 800E 800F 8010 8011 8012 8013 8014 8015 8016 8017 8018 8019 801A 801B 801C 801D 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 809...

Page 38: ...CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OFF 7TH CAPACITOR STEP SWITCH ON OFF 8TH CA...

Page 39: ...columns reactive power values of the capacitors in single phase system are shown CAPACITOR CALCULATION TABLE kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr kVAr k...

Page 40: ...1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Contact Generator Input No Volt Feature Setting Rang...

Page 41: ...Connected to Capacitor Delta Connected to Capacitor Capacitor is not Connected R Phase Connected to Capacitor S Phase Connected to Capacitor T Phase Connected to Capacitor Delta Connected to Capacito...

Reviews: