background image

CP-60

 

 

ENMET  

8

 

 

4.0 Operation 

4.1 Normal Operation Condition 

With the 

CP-60

 

installed as described in Section 3, and in clean air, the 

POWER

 green LED is on, the display is lit, and the 

information on the display is as shown in Figure 6, for the sensor(s) installed in the 

CP-60.

  

The red alarm and fault LEDs are 

not lit. 

 

Example of display with Oxygen Channel 1, Hydrogen Sulfide Channel 2 and Methane Channel 3 Disabled

Figure 6: CP-60

 

Operational Display 

When the 

CP-60

 is first powered up, it goes through a series of momentary screens, which identify the instrument model number, 

serial number and software revision.  After all of the momentary screens have been displayed, the instrument arrives at the Main 
Gas Display showing the gas concentration and unit of measurement in ppm, % or %LEL. 

Depending on transmitter configuration and calibration condition, the furthest right character in the display may flash a letter 
indicating the instrument status. 

4.2 Alarm Conditions 

There are two alarm set points available.  These alarm points are normally set at established safety levels, such as the OSHA 
Permissible Exposure Limit (PEL) for toxic gases or recognized standards below the Lower Explosive Limit for combustible 
gases. 

These alarm set points can be changed within limits; see the maintenance section of this manual for the procedure. 

When the Oxygen, Toxic or combustible gas concentration reaches the alarm set point, the associated red LED is lit, the 
associated relay changes state, and the audio alarm is activated 

Pressing the 

A

LARM 

A

CKN

/A

UDIO 

D

EFEAT

 button can temporally disable the Audio Alarm.  The horn will be disabled for 

about five minutes.  If a second alarm condition occurs during this time the horn will re-activate.  If the alarm condition(s) have 
ended during this time, the horn will not re-activate. 

Differential Setting 

Differential is an optional alarm relay configuration where when an alarm has been triggered, the relay will remain in alarm 
state until the sensor reading has moved the differential “value” in the non-alarm direction.  See example below. 

 

The Alarm 1 differential value is the delay of the 

CP-60

 staying in alarm condition until after the measured reading has returned past the 

alarm point by the differential value.  Example: If the alarm point is 

V

 19.5 and the differential is 2, the 

CP-60

 will go into alarm at 19.5 

and stay in alarm until the reading has risen above 21.5. 

4.3 Alarm Latching 

An instrument is shipped with the alarms in the latching mode.  The alarms may be independently configured in the non-latching 
mode or differential setting by use of the maintenance menu.  See Section 5.2.2, for setting alarm 1 and alarm 2. 

Standard Setting 

  I

N THE LATCHING MODE

: at the cessation of the condition which causes an alarm, the alarm indications do not cease, and the alarm relay 

contacts do not revert to the non-alarm state, until the 

ALARM ACKN/AUDIO DEFEAT

 switch is pressed.  An alarm can also be 

acknowledged by pressing the switch during the alarm condition; then at the cessation of the alarm condition, alarm indications cease and 
alarm relays revert to the non-alarm state. After an alarm is acknowledged, alarms in the latching configuration are re-armed to latch at the 
next alarm condition. 

  I

N THE NON

-

LATCHING MODE

:

 at the cessation of the condition that causes an alarm, the alarm indications automatically cease, and the alarm 

relay contacts revert to the non-alarm state. 

4.4 Audio Defeat 

Pressing the 

AUDIO DEFEAT 

/

 

ALARM ACKNOWLEDGE

 switch during an alarm temporarily silences the audio alarm on the 

CP-

60

 not on the sensor/transmitter.  Relays and alarm LEDs continue to function, in the alarm state, during an alarm condition.  

As long as the alarm condition persists, the audio alarm will “chirp” every 20 seconds.  After the alarm condition clears, the 
audio will continue to “chirp” until the audio switch is pressed. 

 

If after 15 minutes the alarm condition continues the audio alarm will reactivate at full intensity. 

 

If any other alarm condition occurs while the audio alarm has been silenced it will force the audio alarm to reactivate immediately

.

O2 20.9 

Disabld 

H2S 0 

 

O

H

2

PPM

 

CH

4

 

%LEL 

(

Transmitter 3

(

Transmitter 1

(

Transmitter 2

N

OTE

: Programmed Non-active channels 

will display Disabled 

Summary of Contents for CP-60

Page 1: ...ENMET PO Box 979 Ann Arbor MI 48106 0979 www enmet com Manual Part Number 80003 501 MCN 423 07 15 09 CP 60 OPERATION AND MAINTENANCE MANUAL...

Page 2: ...utputs 7 4 0 Operation 8 4 1 Normal Operation Condition 8 4 2 Alarm Conditions 8 4 3 Alarm Latching 8 4 4 Audio Defeat 8 4 5 Display 9 4 6 Operational Menu 9 4 7 Fault Indications 9 5 0 Maintenance 10...

Page 3: ...on Menu Flow Chart 9 Figure 8 CP 60 Maintenance Menu Flow Chart 10 List of Tables Table 1 Relay Factory Default Failsafe Settings 7 Table 2 Default Relay Links 14 Reference Information NOTE important...

Page 4: ...d Keep the items packing material and carton As Is Within 5 days of receipt notify the carrier s local office and request immediate inspection of the carton and the contents After the inspection and a...

Page 5: ...CD with backlight The numerical values of gas concentrations and other information are displayed Visual Alarms Indicators On either sides of the display A red alarm LED for each sensor transmitter ins...

Page 6: ...cts for each of four alarm relays and for the contacts of a fault relay Output Terminals There are two for each of the 4 20 mA outputs Figure 2 CP 60 Interior Features Relays 1 2 3 are programmed to a...

Page 7: ...not ENMET s responsibility The CP 60 should be powered through appropriately sized circuit breakers See Section 6 0 Technical Data Upon supplying power to the CP 60 The green power on LED is lit The d...

Page 8: ...r and gather at the top Consider the density of the gas you want the sensor to detect when you install the sensor Some examples are given below Heavier than Air Gas Sensor Location Bottled LP liquefie...

Page 9: ...Ch 1 3 System Alarm 2 Relay 6 Ch 1 3 System Fault J16 Connector Transmitter 1 4 20mA Input Channel 1 J18 Connector Transmitter 2 4 20mA Input Channel 2 J19 Connector Transmitter 3 4 20mA Input Channel...

Page 10: ...ilsafe Settings Factory Default Settings Position Failsafe Alarm Non Failsafe Alarm Gas Alarm 1 J5 Relay 1 NO Normally Open Normally Closed Channel 1 J5 Relay 1 COM Common Common J5 Relay 1 NC Normall...

Page 11: ...value in the non alarm direction See example below The Alarm 1 differential value is the delay of the CP 60 staying in alarm condition until after the measured reading has returned past the alarm poi...

Page 12: ...on occurs When a transmitter is not connected to an active channel of the CP 60 When a connected Sensor Transmitter reading falls out side of its operation parameters See sensor transmitter manual S S...

Page 13: ...Changes digit indicated by underscore cursor Locks underscored digit and moves cursor to next digit See Section 5 3 7 for changing password instructions O S MAINTENANCE MENU Set Alarm1 Alarm 1 Select...

Page 14: ...he SELECT switch Ch mAXmter 4mA 0000 is displayed Press the SELECT switch that moves the cursor one digit to the right when the last digit is accepted the display move to the full Scale mA Xmtrs menu...

Page 15: ...k in the correct indicator ALARM 1 STD is displayed Press the OPTION switch to toggle between STD and DIFF select the correct indicator Press the SELECT switch to lock in the correct indicator IF STD...

Page 16: ...cated by underscore cursor Locks underscored character and moves cursor to next digit DIFF S O S Changes character indicated by underscore cursor Locks underscored character and moves cursor to next d...

Page 17: ...ect digit Press the SELECT switch which locks the digit in place and moves the cursor one digit to the right Continue this process until the four digit password is complete When a valid password is in...

Page 18: ...isplay is transferred to the Calibration portion of the menu If an invalid password is inserted you are returned to the Enter Maint Menu display After entering a valid password Press the OPTION switch...

Page 19: ...u position Press the SELECT switch to resume the operational display Press the OPTION switch to reenter the maintenance menu at the Calibration position Example Exit Maintenance Menu Flow Chart 5 3 Ch...

Page 20: ...ure 20 to 36 inHg 68 to 133 kPa Mechanical Dimensions 11 x 9 x 6 inches 28 x 23 x 16 cm Weight 8 lbs 3 6 kg Material Engineered thermoplastic with hinged front cover Non magnetic hardware Strain relie...

Page 21: ...aused by the improper use of the product The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this...

Page 22: ...ult in processing delays ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour All instruments sent to ENMET are subject to a mi...

Page 23: ...OD Check one K VISA MasterCard______________________ ________ ________ Card number Expiration Card Code K American Express______________________ ________ ________ Card number Expiration Card Code Name...

Reviews: