CP-60
ENMET
15
5.2.5 Failsafe Configuration
The
CP-60
is factory set in a failsafe configuration. This means that if power is disconnected to the unit, or the relay fails
to properly engage, it fails in such a way that it is in the alarm position.
ENMET
recommends leaving the relay in a failsafe
configuration. However, relay 1 – 5 can be re-configured by using the following procedure.
To change a relay failsafe configuration you must enter the maintenance menu. Press the
OPTION
switch until “Enter Maint
Menu” is displayed then press
SELECT
switch for the Enter Password menu. Enter the valid password as described below.
In the "
Enter Maint Menu
" position
Press the
SELECT
switch "
Enter Password
T
0
" is displayed. Press
SELECT
switch once, to move cursor to next digit,
this will be the first digit of the password.
In the
T
000
position, the underline cursor is under the left digit.
Press the
OPTION
switch to change the left digit; select the correct digit.
Press the
SELECT
switch, which locks the digit in place and moves the cursor one digit to the right.
Continue this process until the four-digit password is complete. When a valid password is inserted in this manner, the
display is transferred to the "
Calibration
" portion of the menu. If an invalid password is inserted you are returned to the
Enter Maint Menu display.
After entering a valid password:
Press the
OPTION
switch until “Relay Failsafes” is displayed
Example: Set Relay Failsafe Configuration Flow Chart
5.2.6 Set Output Span Range
To change 4-20 mA output range. This range is set at the factory and should not be changed, contact
ENMET
for information.
Press the
OPTION
switch to continue to next section of maintenance menu.
Press
OPTION
switch until “Exit maint menu” appears and then press
SELECT
switch to return the instrument to the
Operational Display
Example: Set Output Span Flow Chart
O
S
MAINTENANCE MENU
Relay Failsafes
S
O
S
Relay Failsafes
Changes
Failsafe setting from ON to OFF
Continue pressing
S
ELECT
to cycle through all 5 relays
O
Pressing
O
PTION
changes Failsafe setting from ON to OFF
R: 1 Failsafe ON
Relay Failsafes
R: 2 Failsafe
OFF
O
= Press Option
S = Press Select
O
S
MAINTENANCE MENU
mA Output Span
S
O
S
mA OUTPUT SPAN
Changes
digit indicated by underscore cursor
Locks underscored digit and moves cursor to next digit
O
Press
O
PTION
until the channel to be Set is displayed.
Select: CO
mA OUTPUT SPAN
_ 50 CO
S
O
= Press Option
S = Press Select
Note:
When in maintenance mode the “_” indicates the location of the cursor, the “
I
” block indicates a non-used location.