Installation instructions for professionals
Settings that are not defined
in the settings wizard
The ventilation units are pre-prepared at the factory
in order to shorten the installation time. However,
the possible extras cannot be taken into account for
installation. The settings for the devices connected to the
motherboard must be configured on the control panel.
The following table contains the MD card connections
and their placements on the motherboard.
MD card connections
NTC sensors
The MD card has connections for eight (8) NTC-10 sensors.
Intake
Intended use
X1
Outdoor air temperature measuring TE01
X2
Temperature of supply air after heat recovery unit
TE05
X3
Supply air temperature TE10
Supply air temperature after humidity removal coil
TE07 (only units with humidity removal function)
X4
Exhaust air temperature TE32
X5
Exhaust air temperature before heat recovery TE31
(HP only)
Evaporator fluid pipe temperature TE62 (MDX only)
CG radiator freezing guard TE46 (CG-W only)
X6
Pre-heated exhaust air temperature TE50 (HP only)
X7
Pre-warmed outdoor air temperature TE02 (CHG)
X12
Return water temperature TE45
Analog inputs AI 0-10V
Analog inputs AI1–AI6 are between 0–10V.
These input functions are user-defined.
Intake
Intended use
AI1 (X16)
Humidity transmitter 1
AI2 (X16)
Humidity transmitter 2
Water heater temperature TE80 (Aqua only)
AI3 (X16)
(Free)
Supply air duct pressure PDS10
AI4 (X16)
(Free)
Exhaust air duct pressure PDS30
AI5 (X15)
Carbon dioxide transmitter 1
AI6 (X15)
Carbon dioxide transmitter 2
Analog inputs AI1–AI6 have the following functions available:
Humidity transmitter 1, 2, and 3
Carbon dioxide transmitter 1, 2, and 3
Room temperature transmitter 1, 2, and 3
Outdoor temperature transmitter
Pressure difference transmitter PDE10 and PDE30.
These sensors are used in the constant duct
pressure control.
Changing the temperature setting
Analog inputs AI7–AI8 are between 0–5V.
These intake functions are locked by the program.
MD card connections
AI7 (X29)
Exhaust air humidity RH30
AI8 (X29)
Exhaust air temperature TE30
Analog inputs AI9–AI16 are between 0–10V.
These intake functions are locked by the program.
AI9 (X10)
Supply air filter pressure difference PDE01 (extra)
AI10 (X10)
Exhaust air filter pressure difference PDE31 (extra)
AI11 (X10)
Supply air humidity RH10 (only models with
humidity removal function)
AI12 (X10)
Supply air temperature TE10 (only models with
humidity removal function)
AI13 (X10)
Free
AI14 (X10)
Free
AI15 (X10)
Free
AI15 (X10)
Free
Analog outputs AO 0-10V
Output
Intended use
AO1 (X18)
Supply air blower control voltage
AO2 (X18)
Exhaust air blower control voltage
AO3 (X16)
Cooling control voltage / additional post-heating
control voltage (MDX-E/HP-E/HP-W)
AO4 (X18)
Rotating heat exchanger control voltage
AO5 (X16)
Heating control voltage / compressor power control
voltage (MDX/HP)
AO6 (X15)
Pre-heating control voltage / pre-cooling control
voltage (CHG) / HRW n:o 2 control voltage (Twin
Tropic)
AO7 (X15)
Exhaust air pre-heating control voltage (HP) /
exhaust air drying control voltage (TCG) / LTO
de-frosting control voltage (WGHR)
AO8 (X10)
Hot water production control voltage
Digital outputs (DO), relays, closing contacts.
Intake
Intended use
DO1
On/off control of blowers
DO2
On/Off control of heating
DO3
On/off control of cooling / On/off control of heating
(MDX)
DO4
On/off control of LTO
DO5
On/Off control of air locks
DO6
On/Off control of pre-heating / On/Off control of
pre-cooling / On/Off control of heating circulating
pump (Aqua KIW)
DO7
Time-controlled relay / circulation pump on/off
control PU80 (Aqua) / exhaust air cooling on/off
control (TCG)
DO8
A/AB alarm output, closing
Digital inputs (DI) (buttons and indications)
Connection only to the GND terminal (earthing)! Voltage must
not be connected to digital inputs.
The digital inputs are user-defined
Intake
Intended use
DI1 (X16)
Emergency stop (fixed)
DI2 (X16)
user-defined
PDS10 supply air blower pressure switch /
de-frosting indication (MDX/HP)
DI3 (X16)
user-defined
Overtime (only in Office use)
Summary of Contents for Pingvin XL eAir
Page 20: ...20 9 13 15 11 10 14 Lis varuste 1 2 min 12...
Page 46: ...46...
Page 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 49: ...49 Installationsanvisningar f r yrkesfolk...
Page 50: ...50 Pingvin XL eAir Installationsanvisningar f r ventilationsaggregat Svenska...
Page 68: ...68 9 13 15 11 10 14 Extra tillbeh r 1 2 min 12...
Page 94: ...94...
Page 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 97: ...97 Installasjonsinstrukser for fagfolk...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pingvin XL eAir...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12...
Page 142: ...142...
Page 144: ...144 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 145: ...145 Installation instructions for professionals...
Page 146: ...146 Pingvin XL eAir Installation instructions for the ventilation unit English...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12...
Page 190: ...190...
Page 192: ...192 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 193: ...193...
Page 198: ...198...
Page 199: ...199 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 200: ...200...
Page 204: ...204 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 205: ...205 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 210: ...210...
Page 211: ...211...