Installation instructions for professionals
16
Temperature boost
OFF
Options are ON/OFF.
Select temperature Extract air
temperature
The options are
Extract air temperature
or
Room
temperature average
. To be able to select room
temperature average, you need a separate room
temperature sensor (not included in the basic
delivery).
Max. supply air fan
speed
90%
The maximum allowed speed of the supply air fan
during temperature boost ventilation.
Max. extract air fan
speed
90%
The maximum allowed speed of the extract air fan
during temperature boost ventilation.
17
Cooker hood on,
supply air
50 %
Set the supply air fan speed for when the cooker
hood is on.
Cooker hood on,
extract air
30 %
Set the extract air fan speed for when the cooker
hood is on.
Central vacuum
cleaner on, supply
air
50 %
Set the supply air fan speed for when the central
vacuum cleaner is on.
Central vacuum
cleaner on, extract
air
30 %
Set the extract air fan speed for when the central
vacuum cleaner is on.
Cooker hood and
central vacuum
cleaner on, supply
air
70 %
Set the supply air fan speed for when the cooker
hood and the central vacuum cleaner is on.
Cooker hood and
central vacuum
cleaner on, extract
air
30 %
Set the extract air fan speed for when the cooker
hood and the central vacuum cleaner is on.
Cooker hood, central
vacuum cleaner and
manual overpressure
on, supply air
100 %
Set the supply air fan speed for when the cooker
hood, the central vacuum cleaner and the manual
over pressure is on.
Cooker hood, central
vacuum cleaner and
manual overpressure
on, extract air
30 %
Set the extract air fan speed for when the cooker
hood, the central vacuum cleaner and the manual
over pressure is on.
Summary of Contents for Pingvin XL eAir
Page 20: ...20 9 13 15 11 10 14 Lis varuste 1 2 min 12...
Page 46: ...46...
Page 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 49: ...49 Installationsanvisningar f r yrkesfolk...
Page 50: ...50 Pingvin XL eAir Installationsanvisningar f r ventilationsaggregat Svenska...
Page 68: ...68 9 13 15 11 10 14 Extra tillbeh r 1 2 min 12...
Page 94: ...94...
Page 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 97: ...97 Installasjonsinstrukser for fagfolk...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pingvin XL eAir...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12...
Page 142: ...142...
Page 144: ...144 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 145: ...145 Installation instructions for professionals...
Page 146: ...146 Pingvin XL eAir Installation instructions for the ventilation unit English...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12...
Page 190: ...190...
Page 192: ...192 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 193: ...193...
Page 198: ...198...
Page 199: ...199 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 200: ...200...
Page 204: ...204 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 205: ...205 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 210: ...210...
Page 211: ...211...