176
Temperature sshown
on front of panel
Outside air
temperature
The alternatives are outside air temperature, supply
air temperature and extract air temperature.
5
Use
Home
The options are Home or Office. In the Office mode,
the unit can be switched on only by using a timer.
Temperature control Supply air
Extract air is the
default setting for
units with cooling
functionality.
Supply air
maintains the supply air temperature at
the value specified on the main view. This is the
default setting for units with no cooling functionality.
Room temperature average
or
Extract air c
ompare
the temperature setting in the main view with the
room temperature or extract air temperature and
heat or cool the supply air accordingly. To be able
to use ro
om temperature control
, at least one room
temperature sensor must be
connected.
Extract air
is the default setting for units with cool-
ing functionality.
Cooling
OFF
Options are ON/OFF.
Outside temperature
limit for cooling
17°C
When the outside temperature is below the set
value, no active cooling is allowed.
Heating
ON
Options are ON/OFF.
Outside temperature
limit for heating
25°C
When the outside temperature is above the set
value, no heating is allowed.
Min. supply air
temprature
13°C
This is the minimum temperature for the supply air
when the temperature control value is
Extract air
or
Room temperature average
.
Maximum supply air
temperature
40°C
This is the maximum temperature for the supply air
when the temperature control value is
Extract air
or
Room temperature average
.
Heating/cooling
limitation
OFF
This setting is used if the user wants to prevent
continuous switching between heating or cooling
when the temperature setpoint is very close to the
desired temperature.
Heating
18°C
When the extract air (or the room temperature
average, in room temperature mode) temperature
drops, the heating is not activated until this tem-
perature is reached.
Cooling
24°C
When the extract air (or the room temperature
average, in room temperature mode) increases, the
cooling is not activated until this temperature is
reached.
TE20-21 sensor
OFF
Options are ON/OFF. If both sensors are selected
here, the temperature control uses the mean tem-
perature of the room sensors. If you have installed
only one wall mounting bracket with room tem-
perature sensor, it is TE20.
Room temperature
sensor 1-3
OFF
Options are ON/OFF. These sensors are room tem-
perature transmitters that are connected to the
ventilation unit. The sensors can be included or left
out of the mean room temperature measuring by
setting them on or off.
Summary of Contents for Pingvin XL eAir
Page 20: ...20 9 13 15 11 10 14 Lis varuste 1 2 min 12...
Page 46: ...46...
Page 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 49: ...49 Installationsanvisningar f r yrkesfolk...
Page 50: ...50 Pingvin XL eAir Installationsanvisningar f r ventilationsaggregat Svenska...
Page 68: ...68 9 13 15 11 10 14 Extra tillbeh r 1 2 min 12...
Page 94: ...94...
Page 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 97: ...97 Installasjonsinstrukser for fagfolk...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pingvin XL eAir...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12...
Page 142: ...142...
Page 144: ...144 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 145: ...145 Installation instructions for professionals...
Page 146: ...146 Pingvin XL eAir Installation instructions for the ventilation unit English...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12...
Page 190: ...190...
Page 192: ...192 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 193: ...193...
Page 198: ...198...
Page 199: ...199 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 200: ...200...
Page 204: ...204 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 205: ...205 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 210: ...210...
Page 211: ...211...