Ventilation must be sufficient.
•
If ventilation is not sufficient, the indoor air humidity
will rise, which can cause condensation on cold
surfaces.
•
The indoor air humidity levels must be checked at
regular intervals.
•
The recommended relative room air humidity is
40–45% at most (with room temperature at 20–22°C).
By adhering to these values, the indoor air humidity
remains at a healthy level and the risk of condensation
lowers significantly. Humidity can be measured with
a hygrometer. When air humidity rises over 45%,
ventilation must be boosted. When air humidity drops
under 40%, ventilation can usually be reduced.
•
The cleanliness of filters must be checked regularly.
•
In winter, the exhaust air filter collects dirt faster
than the replacement air filter. This means that the
replacement air flow is reduced, which can lead to a
rise in indoor air humidity, which in turn weakens the
efficiency of heat recovery.
•
More information about cleaning and changing the
filters is in the Maintenance section.
•
Check monthly that the heat exchanger is functioning
correctly, i.e. rotating.
•
More information on the checking and cleaning the
heat exchanger is in the Maintenance section.
•
If ventilation unit is not used for a long time, it can
be shut down as long as the fresh air intake vent and
exhaust air blowout vent are covered.
•
This prevents humidity from condensing on the
electric motors of blower, for example.
•
In the autumn, before the beginning of heating
period and before beginning cooling (if the unit has
a cooling function), the condensation water sewage
functionalities must be checked by pouring water in
the condensation water sewer and making sure that
the water drains away.
General instructions
Do not shut down the ventilation unit. The
ventilation unit must always be kept in operation
at the power level set by the ventilation system
designer.
NOTE
Using the eAir control panel
Ventilation is used primarily with modes. The modes in use
can be seen in the control panel main screen. The user can
choose the best mode for each situation: At home, Away,
Boost, Overpressure, Silent, or Max. cooling / Max. heating.
The Silent and Max. cooling / Max. heating modes must
be activated separately from the Settings > Modes menu
before they are shown in the Modes menu. The Modes
menu can be accessed by tapping the round button in
the middle of the control panel main screen.
Eco mode can be activated in all modes except in Max.
cooling / Max. heating mode. Eco mode stops post-
heating and active cooling, and maximizes the use of heat
recovery. Heat recovery is 100% until outdoor temperature
reaches the outdoor temperature limit of heating, or until
supply air temperature reaches the supply air temperature
maximum limit. If the supply air temperature drops below
the minimum temperature, post-heating activates and
keeps the supply air temperature at minimum level.
The circle around the operating mode button changes
its color depending on what the ventilation unit is doing.
The circle is green when heat recovery is active; orange
and red when heating is active, and blue when cooling is
active.
The other functions of the ventilation unit can be found
in the Main menu. The menu can be accessed by tapping
the arrow at the bottom of the control panel main screen.
The main menu consists of the following submenus:
Time programs, Measurements, Alarm, Settings, System
information, Maintenance, and eAir web settings For more
information on menus, see the Instructions.
If the system has an automatic alarm, it is shown in yellow
in the control panel main screen. The most common
alarm is the one about changing filters. The reason for the
alarm must always be checked. Check the Alarms menu
for the possible reason for the alarm and the instruction to
how to acknowledge it.
Summary of Contents for Pingvin XL eAir
Page 20: ...20 9 13 15 11 10 14 Lis varuste 1 2 min 12...
Page 46: ...46...
Page 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 49: ...49 Installationsanvisningar f r yrkesfolk...
Page 50: ...50 Pingvin XL eAir Installationsanvisningar f r ventilationsaggregat Svenska...
Page 68: ...68 9 13 15 11 10 14 Extra tillbeh r 1 2 min 12...
Page 94: ...94...
Page 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 97: ...97 Installasjonsinstrukser for fagfolk...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pingvin XL eAir...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12...
Page 142: ...142...
Page 144: ...144 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 145: ...145 Installation instructions for professionals...
Page 146: ...146 Pingvin XL eAir Installation instructions for the ventilation unit English...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12...
Page 190: ...190...
Page 192: ...192 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 193: ...193...
Page 198: ...198...
Page 199: ...199 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 200: ...200...
Page 204: ...204 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 205: ...205 Enervent Zehnder Oy Kipin tie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com...
Page 210: ...210...
Page 211: ...211...