57
IOM, BS/BT Models
Enertech Global
H: EXCESSIVE HEAD PRESSURE IN HEATING MODE
Low air flow
See E: Noisy blower and low air flow.
I: AIR COIL FREEZES OVER IN COOLING MODE
Air flow
See E: Noisy blower and low air flow.
Blower motor
Motor not running or running too slow. Motor tripping off on overload. Check for overheated blower motor
and tripped overload. Replace motor if defective.
Panels
Panels not in place.
Low air flow
See E: Noisy blower and low air flow.
J: WATER DRIPPING FROM UNIT
Unit not level
Level unit.
Condensation drain line plugged
Unplug condensation line.
Water sucking off the air coil in
cooling mode
Too much airflow. Duct work not completely installed. If duct work is not completely installed, finish duct
work. Check static pressure and compare with air flow chart in spec manual under specific models section.
If ductwork is completely installed it may be necessary to reduce CFM.
Water sucking out of the
drain pan
Install an EZ-Trap or P-Trap on the drain outlet so blower cannot suck air back through the drain outlet.
Section 12: Troubleshooting