Manual Heat Pump Model HHPM-V.2- SEP 2012
21
4.3 User Setting Page
Press
at homepage.
User Setting
Press
to enter.
DESCRIPTION
MEANING
FACTORY SETTING
TANK SETTING
SET TANK TEMP. FOR STOP HEAT PUMP
50
TEMP DIFF 1
SET DROP TEMP. FOR START HEAT PUMP
2
TEMP DIFF 2
SET DROP TEMP. FOR START HEATER (RESERVE)
5
UNIT ON DELAY
SET DELAY TIME FOR START HEAT PUMP
5
OUTLET SETTING
SET OUTLET HOT WATER TEMP. OF HEAT PUMP
60
OUTLET DIFF
SET DIFFERENTIAL OF OUTLET HOT WATER TEMP.
1
HIGH T. CUT OUT
SET CUTOUT TEMP. OF HOT WATER OUTLET. IF
TEMP. > SET THEN STOP HEAT PUMP.
70
HIGH T. CUT IN
SET CUT IN TEMP. OF HOT WATER OUTLET. IF
TEMP. < SET THEN START HEAT PUMP.
65
LOW T. CUT OUT
RESERVE NOT USE.
10
LOW T. CUT IN
RESERVE NOT USE.
20
DEF. START T.
RESERVE NOT USE.
-2
DEF. STOP T.
RESERVE NOT USE.
8
DEF. TIME
RESERVE NOT USE.
10
DEF. INTERVAL
RESERVE NOT USE.
30
AUTO RESTART
HEAT PUMP AUTO START IF POWER WAS CUT OUT
AND THEN ON , 1= ON , 0 = OFF
1
TIMER FUNCTION
0 = DISABLE , 1 = ENABLE
0
MENU
1
USER
SET
SET
TIME
SET
FAULT
LIST
ENT
STATUS
HISTORY