Technical specifications
84
ESE 604 DHG (ES) DIN
Status: October 2018
Name
Value
Unit
Setting up height above sea
level
max. 2,000
[m]
Temperature
-20 to +40
[°C]
Relative air humidity
max. 95, not con-
densing
[%]
Table 8.2: Ambient conditions for the generator
Name
Value
Unit
Setting up height above sea
level
< 100
[m]
Temperature
< 25
[°C]
Relative air humidity
< 30
[%]
Table 8.3: Standard reference conditions for the generators
Power reduction
for each addi-
tional
Unit
1 %
100
[m]
4 %
10
[°C]
Table 8.4: Generator power reduction dependent on standard reference
conditions
Line
max. line length
Unit
HO 7 RN-F (NSH öu) 1,5 mm
2
60
[m]
HO 7 RN-F (NSH öu) 2,5 mm
2
100
[m]
Table 8.5: Maximum line length of the distribution network as a function of
the cable cross-section
WARNING!
The general limitation of 100 m for the overall length was
selected in the interest of safe handling during practical
use. Larger dimensioning of the distribution network is
only to be undertaken by a qualified electrician or trained
personnel.
Ambient conditions
Standard reference
conditions
Reduced power
Distribution network
Summary of Contents for ESE 604 DHG DIN
Page 11: ...General information Status at October 2018 ESE 604 DHG ES DIN 11 Notes...
Page 26: ...General Safety Regulations 26 ESE 604 DHG ES DIN Status October 2018 Notes...
Page 49: ...Operate power generator ESE 604 DHG DIN Status at October 2018 ESE 604 DHG ES DIN 49 Notes...
Page 81: ...Troubleshooting Status at October 2018 ESE 604 DHG ES DIN 81 Notes...
Page 85: ...Technical specifications Status at October 2018 ESE 604 DHG ES DIN 85 Notes...