4 Electrical installation
RMS 621
20
Hauser
Terminal layout of the temperature expansion card (RMS621A-TA)
!
Note!
The current/PFM/pulse input inputs or RTD inputs of individual cards are not galvanically isolated.
There is an isolation voltage of 500 V between the above mentioned inputs and outputs in differing
slots as well as the outputs of individual cards. Similar terminals are internally linked.
4.2.5
Connecting the remote display/operating module
Function description
The remote display is an innovative expansion to the powerful DIN rail mounted RMS621 unit. For
the user this means that the calculation unit can be installed technically correct and the display and
operating module can be mounted in an easily accessible and user friendly position. The display can
be connected to a DIN rail mounted unit that has already got an integrated display/operating
module as well as one without a display/operating module. In order to connect the remote display
a four core cable is supplied, other components are not required.
!
Note!
Only one remote display/operating unit can be connected to a DIN rail mounted unit and Vica Versa
(point to point).
Terminal (Pos.no.)
Terminal layout
Slot
In- and outputs
117
+ RTD supply 1
B, C, D top front
(B I, C I,
D I)
RTD input 1
116
+ RTD sensor 1
115
- RTD sensor 1
114
- RTD supply 1
121
+ RTD supply 2
B, C, D top back
(B II, C
II, D II)
RTD input 2
120
+ RTD sensor 2
119
- RTD sensor 2
118
- RTD supply 2
142
Relay 1 Common (COM)
B, C, D bottom front
(B
III, C III, D III)
Relay1
143
Relay 1 normally open (NO)
152
Relay 2 Common (COM)
Relay 2
153
Relay 2 normally open (NO)
131
+ 0/4 to 20 mA/pulse output 1
B, C, D bottom middle
(B
IV, C IV, D IV)
Current/pulse output 1 active
132
- 0/4 to 20 mA/pulse output 1
133
+ 0/4 to 20 mA/pulse output 2
Current/pulse output 2 active
134
- 0/4 to 20 mA/pulse output 2
135
+ Pulse output 3 (Open collector)
B, C, D bottom back
(B V,
C V, D V)
Passive pulse output
136
- Pulse output 3
137
+ Pulse output 4 (Open collector)
Passive pulse output
138
- Pulse output 4
Summary of Contents for RMS621
Page 1: ...BA127R 09 en 08 04 510 04788 Software Version 2 0 Operating manual RMS 621 Energy manager ...
Page 6: ...RMS 621 6 Endress Hauser ...
Page 23: ...RMS 621 5 Operation Endress Hauser 23 5 1 2 Display Quick Setup ...
Page 88: ......
Page 90: ...www endress com worldwide BA 127R 09 en 08 04 510 04788 FM SGML6 0 ...