RMS 621
6 Commissioning
Hauser
47
Type
Negative
Positive
Makes it possible to transmit pulses in a positive or negative
direction (e.g. for external electronic totalizers):
•
ACTIVE: the device internal power supply is used (+24 V)
•
PASSIVE: external power supply necessary
•
POSITIVE: rest peak at 0 V ("active-high")
•
NEGATIVE: rest peak at 24 V ("active-low") or external
power supply
Unit
g, kg, t
for mass sum
signal source
kWh, MWh, MJ
for heat
sum signal source
dm3
for flow signal source
Pulse output engineering unit.
!
Note!
Pulse engineering unit depends on the signal source selected.
Unit value
0.001 to 10000.0
1.0
Setting as to which value a pulse corresponds to (unit/pulse).
!
Note!
The max. possible output frequency is 50 Hz. The suitable
pulse value can be determined as follows:
Set width
Yes
No
The pulse width limits the max. possible output frequency of
the pulse output.
Standard = pulse width fixed, i.e. always 100 ms.
User defined = pulse width can be freely configured.
Pulse width
0.01 to 10.00 s
Configuration of the pulse width suiting the external totalizer.
The maximum permitted pulse width can be calculated as
follows:
Function (menu item)
Parameter setting
Description
PASSIVE-NEGATIVE
ACTIVE-NEGATIVE
ACTIVE-POSITIVE
PASSIVE-POSITIVE
ACTIVE
Internal
power supply
24 V DC
Push-
Pull
For continuous currents up to 15 mA
12
12
13
13
Short-circuit
proof output
Short-circuit
proof output
Open
Collector
External
power supply
U
= 30 V DC
max
PASSIVE
For continuous currents up to 25 mA
NEGATIVE pulses
POSITIVE pulses
Pulse value
Estimated max. flow (end value)
Desired max. output frequency
2 x max. output frequency
Pulse width
Summary of Contents for RMS621
Page 1: ...BA127R 09 en 08 04 510 04788 Software Version 2 0 Operating manual RMS 621 Energy manager ...
Page 6: ...RMS 621 6 Endress Hauser ...
Page 23: ...RMS 621 5 Operation Endress Hauser 23 5 1 2 Display Quick Setup ...
Page 88: ......
Page 90: ...www endress com worldwide BA 127R 09 en 08 04 510 04788 FM SGML6 0 ...