Applications
Number of measurement points
The number of measurement points vary according to the unit model and application. For further
details, please see the table for applications/measurement points.
In general, the following measurements are possible:
Up to 3 measurement points with the input values (measurements) q, T. T
One measurement point is covered by the basic unit. Expansion cards are required if further
measurement points are to be added. Each expansion card is fitted with outputs
(analogue/impulse) for retransmission of process values. Relay outputs are also available.
Diagram/calculation formula
T
2
q
T
1
Heat output (heating)
E = q
(T
1,
p) [h (T
1
) – h (T
2
)]
Heat input (cooling)
E = q
(T
1,
p) [h (T
2
) – h (T
1
)]
E: Heat
quantity
q: Operating
volume
:
Density
T
1
:
Temperature in inflow
T
2
:
Temperature in return
p:
Average operating pressure
h
(T
1
):
Specific Enthalpy of water at temperature 1
h
(T
2
):
Specific Enthalpy of water at temperature 2